Plan Review Notes For Permit 01031035 |
Permit Number |
01031035 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-05 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE SHOW MIN BRANCH CIRCUIT | | #`S ON PLANS AND CORRELATE CIRCUITS | | WITHPANEL SCHEDULES SUBMITTED. | | | | 2)NOTE: PLEASE NOTE THAT EGRESS | | LIGHTINGIN STAIRWELL IS SHOWN BEING | | SWITCHED. | | EGRESS LIGHTING IN STAIRS NEED TO BE | | POWERED BY CONTINOUS POWER. | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION FOR | | FEED TO PANELS. 100A DISC SHOWN FEEDING | | TWO 100A PANELS WITH LOADS EXCEEDING | | OVER CURRENT PROTECTION. | | | | 4)NOTE: PLEASE CLARIFY TYPE OF CONDUIT | | PR EQUIPMENT GROUND BETWEEN DISCAND | | PANEL. | | | | PLEASE SUBMIT THE ABOVE INFORMTATION | | FORREVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|