2001-04-05 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW MIN BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE CIRCUITS
 WITHPANEL SCHEDULES SUBMITTED.
  
 2)NOTE: PLEASE NOTE THAT EGRESS
 LIGHTINGIN STAIRWELL IS SHOWN BEING
 SWITCHED.
 EGRESS LIGHTING IN STAIRS NEED TO BE
 POWERED BY CONTINOUS POWER.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION FOR
 FEED TO PANELS. 100A DISC SHOWN FEEDING
 TWO 100A PANELS WITH LOADS EXCEEDING
 OVER CURRENT PROTECTION.
  
 4)NOTE: PLEASE CLARIFY TYPE OF CONDUIT
 PR EQUIPMENT GROUND BETWEEN DISCAND
 PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMTATION
 FORREVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  