Plan Review Notes
Plan Review Notes For Permit 01031024
Permit Number 01031024
Review Stop M
Sequence Number 1
Notes
Date Text
2001-05-31 00:00:00OKED PER JOHN LEECH 04/02/2001
2001-04-02 00:00:00PROVISO;
  
 1.A/C EQUIPMENT IS NOT LARGE ENOUGH.
 2009 SQ FT UNDER A/C AND 1560 CFM'S.
 EQUIPMENT SHOULD BE 4 TON.
  
 2.R/A REQUIRED FROM MASTER SUITE.
  
 3.REVISED DRAWINGS REQUIRED BEFORE ROUGH
 A/C INSPECTION.
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377