Date |
Text |
2001-04-27 00:00:00 | CHECKLIST: |
| 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| BRING STAMPED DRAWINGS AND RECEIPT. |
| 2-NOTICE OF COMMENCEMENT DESCRIPTION OF |
| WORK DOESN'T MATCH THE SCOPE OF WORK |
| DECLARED ON THIS PERMIT APPLICATION. |
| 3-SPECIFY DESIGN PRESSURES CALCULATED |
| FOR THE EXTERIOR OPENINGS AS PER |
| SECTION 1606 SBC 1997. |
| 4-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS AND SEC. 2405.2 SBC 1997. |
| 5-COMPLETE FLOOR AND FOUNDATION PLANS |
| SHOWING THE OUTSIDE STEPS. |
| NOTE: A LANDING IS REQUIRED @ EXTERIOR |
| DOORS. SEE PLANS AND SECTION 1012.1.6 |
| OF SBC 1997. |
| 6-PROVIDE ATTIC ACCESS AT GARAGE AND |
| SECOND FLOOR ROOF. SEC 2309.6 SBC 1997 |
| 7-PROVIDE COMPLETE DESIGN CERTIFICATION |
| FOR BUILDING CODE COMPLIANCE FORM. |
| ATTACHED (PROVIDE TWO COPIES). |
| 8-OWNER/AGENT TO SIGN AND DATE THE |
| ENERGY CALCULATIONS (PROVIDE 2 COPIES) |
| 9-SPECIFY BEAMS AND CONNECTORS. |
| SEC 104.2.2 CITY AMENDMENTS TO SBC/97 |
| 10-SPECIFY ALL COLUMNS AND TOP AND BOTT. |
| CONNECTORS. SEC 104.2.2 CITY AMENDMENT |
| 11-SPECIFY CALCULATED UPLIFT LOADS AND |
| PROVIDE ANCHOR SCHEDULE. SEC 1606 SBC |
| 12-PROVIDE COMPLETE SECTION DETAIL THRU |
| BALCONY. SPECIFY CONSTRUCTION, ANCHORS |
| AND MATERIALS TO BE USED.SECTION |
| 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| 13-NEED SECOND FLOOR FRAMING PLAN. |
| NOTE: EXISTING RAFTERS WERE DESIGNED |
| TO CARRY A ROOF LOAD. FLOOR LOADS ARE |
| DIFFERENT. SEE SECTIONS 1603 AND 1604 |
| OF SBC 1997. PROVIDE COMPLETE |
| STRUCTURAL ANALYSIS AND WOOD SPECS IF |
| USING THE EXISTING FRAMING TO CARRY |
| THE NEW LOADS. |
| SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| 14-PROVIDE COMPLETE CONSTRUCTION DETAILS |
| AND SPECS FOR CONSTRUCTION OF PERGOLA. |
| SEC. 104.2.2 CITY AMENDMENTS. |
| 15-PROVIDE SMOKE DETECTORS AT FIRST AND |
| SECOND FLOOR. SEC 905.2 SBC 1997. |
| 16-SPECIFY ATTIC VENTILATION. SECTION |
| 2309.7 SBC 1997. |
| 17-PROVIDE AREA TABULATION |
| 18-STORM SHUTTERS: |
| A)PROVIDE KEY PLAN AND COMPLETE |
| INSTALLATION SCHEDULE AS PER CITY |
| SAMPLE ATTACHED. |
| B)CLEARLY MARK ON STORM PANELS DRAWINGS |
| THE SPECIFIC MOUNTING CONDITIONS AND |
| ANCHOR TYPE TO BE USED ACCORDING TO |
| THE MEAN ROOF HEIGHT,DESIGN PRESSURES, |
| PANEL SPAN, EDGE DISTANCE, CONNECTION |
| TYPE AND STRUCTURE TO BE ATTACHED TO |
| (CONCRETE BLOCK OR WOOD). |
| 19-TRUSS DRAWINGS: |
| A)ARCHITECT OF RECORD TO REVIEW ALL |
| TRUSS DRAWINGS PRIOR TO SUBMITTAL. |
| B)ENGINEER TO SIGN, SEAL AND DATE THE |
| TRUSS LAYOUT AS REQUIRED BY CHAPTER |
| 471 OF FLORIDA STATUTES. |
| C)TRUSS LAYOUT AND ARCHITECT'S ROOF |
| FRAMING PLANS ARE DIFFERENT. REVISE |
| EITHER ONE TO MATCH. |
| D)TRUSS LAYOUT HAVE THE WRONG ADDRESS |
| AND OWNER OF THIS HOUSE. |
| E)UPDATE TRUSS DESIGN CRITERIA TO ASCE |
| 7-95 FOR 145MPH OR SBC 1997 FOR 110MPH |
| ACCORDING TO THE DESIGN CRITERIA USED |
| BY THE ARCHITECT OF RECORD. |
| F)PROVIDE COMPLETE SETS OF ENGINEERED |
| TRUSSES (REVIEWED BY THE ARCHITECT) |
| 20-PROVIDE 2 COPIES OF PRODUCT APPROVALS |
| A)ENTRY DOOR. |
| B)SINGLE HUNG WINDOWS. |
| C)GARAGE DOOR (IF REPLACED) |
| D)WINDOW MULLIONS. |
| E)FRENCH DOORS. |
| F)GARAGE SWING DOOR. |
| G)AWNING WINDOWS. |
| 21-SEE PLANS FOR ADDITIONAL COMMENTS |
| AND PLEASE RETURN REVIEWED SET AFTER |
| CORRECTIONS ARE DONE TO THE ORIGINAL |
| DRAWINGS, IN ORDER TO EXPEDITE THE |
| REVIEW PROCESS. |
| 22-PROVIDE STRUCTURAL BUCK DETAILS FOR |
| DOORS AND WINDOWS. ALSO, FOR GARAGE |
| DOOR IF IT'S GOING TO BE REPLACED. |
| SEC. 104.2.2 CITY AMENDMENTS. |
| |
| NOTE: SURVEY SAYS FLOOD ZONE B. ACTUAL |
| FLOOD ZONE IS C. |
| |
| |