Plan Review Notes
Plan Review Notes For Permit 01030864
Permit Number 01030864
Review Stop R
Sequence Number 1
Notes
Date Text
2001-04-27 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-NOTICE OF COMMENCEMENT DESCRIPTION OF
 WORK DOESN'T MATCH THE SCOPE OF WORK
 DECLARED ON THIS PERMIT APPLICATION.
 3-SPECIFY DESIGN PRESSURES CALCULATED
 FOR THE EXTERIOR OPENINGS AS PER
 SECTION 1606 SBC 1997.
 4-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 5-COMPLETE FLOOR AND FOUNDATION PLANS
 SHOWING THE OUTSIDE STEPS.
 NOTE: A LANDING IS REQUIRED @ EXTERIOR
 DOORS. SEE PLANS AND SECTION 1012.1.6
 OF SBC 1997.
 6-PROVIDE ATTIC ACCESS AT GARAGE AND
 SECOND FLOOR ROOF. SEC 2309.6 SBC 1997
 7-PROVIDE COMPLETE DESIGN CERTIFICATION
 FOR BUILDING CODE COMPLIANCE FORM.
 ATTACHED (PROVIDE TWO COPIES).
 8-OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS (PROVIDE 2 COPIES)
 9-SPECIFY BEAMS AND CONNECTORS.
 SEC 104.2.2 CITY AMENDMENTS TO SBC/97
 10-SPECIFY ALL COLUMNS AND TOP AND BOTT.
 CONNECTORS. SEC 104.2.2 CITY AMENDMENT
 11-SPECIFY CALCULATED UPLIFT LOADS AND
 PROVIDE ANCHOR SCHEDULE. SEC 1606 SBC
 12-PROVIDE COMPLETE SECTION DETAIL THRU
 BALCONY. SPECIFY CONSTRUCTION, ANCHORS
 AND MATERIALS TO BE USED.SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 13-NEED SECOND FLOOR FRAMING PLAN.
 NOTE: EXISTING RAFTERS WERE DESIGNED
 TO CARRY A ROOF LOAD. FLOOR LOADS ARE
 DIFFERENT. SEE SECTIONS 1603 AND 1604
 OF SBC 1997. PROVIDE COMPLETE
 STRUCTURAL ANALYSIS AND WOOD SPECS IF
 USING THE EXISTING FRAMING TO CARRY
 THE NEW LOADS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 14-PROVIDE COMPLETE CONSTRUCTION DETAILS
 AND SPECS FOR CONSTRUCTION OF PERGOLA.
 SEC. 104.2.2 CITY AMENDMENTS.
 15-PROVIDE SMOKE DETECTORS AT FIRST AND
 SECOND FLOOR. SEC 905.2 SBC 1997.
 16-SPECIFY ATTIC VENTILATION. SECTION
 2309.7 SBC 1997.
 17-PROVIDE AREA TABULATION
 18-STORM SHUTTERS:
 A)PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE AS PER CITY
 SAMPLE ATTACHED.
 B)CLEARLY MARK ON STORM PANELS DRAWINGS
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR WOOD).
 19-TRUSS DRAWINGS:
 A)ARCHITECT OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL.
 B)ENGINEER TO SIGN, SEAL AND DATE THE
 TRUSS LAYOUT AS REQUIRED BY CHAPTER
 471 OF FLORIDA STATUTES.
 C)TRUSS LAYOUT AND ARCHITECT'S ROOF
 FRAMING PLANS ARE DIFFERENT. REVISE
 EITHER ONE TO MATCH.
 D)TRUSS LAYOUT HAVE THE WRONG ADDRESS
 AND OWNER OF THIS HOUSE.
 E)UPDATE TRUSS DESIGN CRITERIA TO ASCE
 7-95 FOR 145MPH OR SBC 1997 FOR 110MPH
 ACCORDING TO THE DESIGN CRITERIA USED
 BY THE ARCHITECT OF RECORD.
 F)PROVIDE COMPLETE SETS OF ENGINEERED
 TRUSSES (REVIEWED BY THE ARCHITECT)
 20-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 A)ENTRY DOOR.
 B)SINGLE HUNG WINDOWS.
 C)GARAGE DOOR (IF REPLACED)
 D)WINDOW MULLIONS.
 E)FRENCH DOORS.
 F)GARAGE SWING DOOR.
 G)AWNING WINDOWS.
 21-SEE PLANS FOR ADDITIONAL COMMENTS
 AND PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS, IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 22-PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS. ALSO, FOR GARAGE
 DOOR IF IT'S GOING TO BE REPLACED.
 SEC. 104.2.2 CITY AMENDMENTS.
  
 NOTE: SURVEY SAYS FLOOD ZONE B. ACTUAL
 FLOOD ZONE IS C.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ, BUILDING PLAN REVIEWER, AT
 659-8096 EXT. 8232.