2001-03-26 00:00:00DENIED;
  
 1.LIST CFM'S FOR EACH DROP.
  
 2.SIZE AND ROUTE OF DUCT BOARD IS
 UNCLEAR. COMPLY WITH COUNTY WIDE
 AMENDMENTS 104.2.
  
 3.MASTER BEDROOM SUITE REQUIRED A R/A IF
 SUPPLY AIR IS 300 CFM'S OR MORE.
  
 A/C PLAN REVIEW BY;