2001-03-27 00:00:00 | *************** UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE ELECTRICAL LEGEND, |
| YOU SHOW THE REQ`D EGRESS LIGHTING AS |
| CEILING J-BOXES. PLEASE SEE 210-70 FOR |
| THE REQ`D LIGHTING FIXTURES. |
| |
| 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| PLEASE NOTE THAT MORETHAN 50% OF THE |
| STRUCTURE IS BEING WIRED. NEED TO BRING |
| SD REQ`MENTS UP TO CODE. |
| |
| 3) NOTE: PLEASE SHOW ALL OUTLETS |
| SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| PROTECT--ED PER 210-8-A-6. |
| |
| 4)NOTE: PLEASE SUBMIT PANEL SCHEDULE |
| WITH THE REQ`D CIRCUITS SHOWN. |
| PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 5) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| BY 210-52E OF THE NEC. EXSITING? |
| |
| 6)NOTE: PLEASE SHOW ANY NEW A/C |
| EQUIPMENT ON ELECTRICAL DRAWING. PLEASE |
| SHOW |
| REQ`D GFI 309.1 OF THE MECH CODE AND |
| 210-63. PLEASE SHOW DISCONNECT(S) PER |
| 440-11. |
| |
| 7)NOTE: PLEASE PLACE NOTE ON PLANS THAT |
| AREA WHERE CLOSET MUST MAINTAIN |
| CLEARENCE REQ`D PER 110-26 AND 384-7. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |