2001-03-27 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE ELECTRICAL LEGEND,
 YOU SHOW THE REQ`D EGRESS LIGHTING AS
 CEILING J-BOXES. PLEASE SEE 210-70 FOR
 THE REQ`D LIGHTING FIXTURES.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE THAT MORETHAN 50% OF THE
 STRUCTURE IS BEING WIRED. NEED TO BRING
 SD REQ`MENTS UP TO CODE.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 4)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 WITH THE REQ`D CIRCUITS SHOWN.
 PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC. EXSITING?
  
 6)NOTE: PLEASE SHOW ANY NEW A/C
 EQUIPMENT ON ELECTRICAL DRAWING. PLEASE
 SHOW
 REQ`D GFI 309.1 OF THE MECH CODE AND
 210-63. PLEASE SHOW DISCONNECT(S) PER
 440-11.
  
 7)NOTE: PLEASE PLACE NOTE ON PLANS THAT
 AREA WHERE CLOSET MUST MAINTAIN
 CLEARENCE REQ`D PER 110-26 AND 384-7.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  