Plan Review Notes
Plan Review Notes For Permit 01030667
Permit Number 01030667
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-23 00:00:00*************** UNSAT ****************
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC. GRADE LEVEL
 ACCESS FROM GARAGE.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL AT DETACHED GARAGE.
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 3) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50 AT DEATCHED GARAGE.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372