Plan Review Notes For Permit 01030667 |
Permit Number |
01030667 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-23 00:00:00 | *************** UNSAT **************** | | | | 1) PLEASE NOTE EITHER MISSING EGRESS | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | PER 210-70 OF THE NEC. GRADE LEVEL | | ACCESS FROM GARAGE. | | | | 2) PLEASE CLARIFY EQUIPMENT GROUNDING | | METHOD BETWEEN FIRST MEANS OF | | DISCONNECTAND PANEL AT DETACHED GARAGE. | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | 3) NOTE: PLEASE SHOW GROUNDING | | ELECTRODEGOING TO BUILDING STEEL AND | | COLD WATER | | PER 250-50 AT DEATCHED GARAGE. | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE AREANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|