2001-04-05 00:00:00 | APPROVED WITH PROVISO: |
| |
| 1-PROVIDE SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS. SEC. 2405.2 SBC 1997. |
| 2-CORRECT AREA CALCULATIONS. |
| 3-UPDATE GENERAL NOTES. WE ARE USING THE |
| SBC 1997, NOT SFBC. |
| 4-REVISE THE DESIGN CERTIFICATION FOR |
| BUILDING CODE COMPLIANCE FORM. SEE |
| COMMENTS ON SUBMITTED FORM. |
| 5-STORM PANELS UNDER A SEPARATE PERMIT: |
| -PRODUCT APPROVAL EXPIRED. |
| -PROVIDE A KEY PLAN AND A COMPLETE |
| INSTALLATION SCHEDULE. |
| -CLEARLY INDICATE ON STORM PANEL DWGS |
| THE MOUNTING CONDITIONS AND ANCHOR |
| TYPE AND SPACING TO BE USED ACCORDING |
| TO THE MEAN ROOF HEIGHT, DESIGN |
| PRESSURES, PANEL SPAN, EDGE DISTANCE, |
| CONNECTION TYPE AND STRUCTURE TO BE |
| ATTACHED TO (CONCRETE BLOCK). |
| 6-PROVIDE PRODUCT APPROVAL FOR: |
| -ENTRY DOORS WITH SIDELITES SINGLE |
| ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS |
| -SINGLE EXTERIOR DOORS PRODUCT APPROVAL |
| EXPIRED. |
| -STOREFRONT SYSTEM DRAWINGS ARE NOT |
| CLEAR AND SOME SIZES SHOWN ON THE |
| ARCHITECTURAL DRAWINGS ARE BIGGER THAN |
| THE ONES COVERED BY THIS PRODUCT |
| APPROVAL. NEED PRODUCT APPROVAL FOR |
| THOSE SIZES AS WELL. |
| -SLIDING GLASS DOORS DRAWINGS ARE NOT |
| LEGIBLE. |
| -FIXED GLASS WINDOWS WITH THE SIZE |
| SHOWN ON ARCHITECTURAL PLANS. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 659-8096 EXT. 8232. |