Plan Review Notes
Plan Review Notes For Permit 01030624
Permit Number 01030624
Review Stop R
Sequence Number 1
Notes
Date Text
2001-04-05 00:00:00APPROVED WITH PROVISO:
  
 1-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEE PLANS. SEC. 2405.2 SBC 1997.
 2-CORRECT AREA CALCULATIONS.
 3-UPDATE GENERAL NOTES. WE ARE USING THE
 SBC 1997, NOT SFBC.
 4-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. SEE
 COMMENTS ON SUBMITTED FORM.
 5-STORM PANELS UNDER A SEPARATE PERMIT:
 -PRODUCT APPROVAL EXPIRED.
 -PROVIDE A KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE.
 -CLEARLY INDICATE ON STORM PANEL DWGS
 THE MOUNTING CONDITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO THE MEAN ROOF HEIGHT, DESIGN
 PRESSURES, PANEL SPAN, EDGE DISTANCE,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (CONCRETE BLOCK).
 6-PROVIDE PRODUCT APPROVAL FOR:
 -ENTRY DOORS WITH SIDELITES SINGLE
 ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS
 -SINGLE EXTERIOR DOORS PRODUCT APPROVAL
 EXPIRED.
 -STOREFRONT SYSTEM DRAWINGS ARE NOT
 CLEAR AND SOME SIZES SHOWN ON THE
 ARCHITECTURAL DRAWINGS ARE BIGGER THAN
 THE ONES COVERED BY THIS PRODUCT
 APPROVAL. NEED PRODUCT APPROVAL FOR
 THOSE SIZES AS WELL.
 -SLIDING GLASS DOORS DRAWINGS ARE NOT
 LEGIBLE.
 -FIXED GLASS WINDOWS WITH THE SIZE
 SHOWN ON ARCHITECTURAL PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.