Plan Review Notes For Permit 01030589 |
Permit Number |
01030589 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-02 00:00:00 | DENIED; | | | | 1.PAGE A1 TOILET ROOM MEASUREMENTS ARE | | NOT CORRECT. FLOOR PLAN, SAME PAGE, | | BATHROOM SIZE IS 7'X7'. | | | | 2.SHOW ON PLANS COMPLIANCE TO 94 SPC | | TABLE 407 MINIMUM PLUMBING FIXTURES | | REQUIRED. (NUMBER OF PEOPLE PER SHIFT) | | | | 3.ONE DRINKING FOUNTAIN IS REQUIRED PER. | | TABLE 407. DRINKING FOUNTAIN SHALL | | COMPLY WITH FACBC 4.1.3(10) AND 4.15. | | PROVISIONS SHALL BE MADE FOR PEOPLE | | WHO HAVE TROUBLE BENDING OR STOOPING. | | | | 4.PAGE P (RISER DIAGRAM) URINAL IS UN- | | VENTED. | | | | 5.FLOOR DRAIN; | | A.WHAT WILL DRAIN INTO FLOOR DRAIN | | B.SHOULD HAVE A DEEP SEAL. | | C.IS NOT VENTED SEE TABLE 908.1. | | | | 6.PAGE A-2 (CABINET DETAIL) SINK TO | | COMPLY WITH FACBC 4.24.2 THRU 4.24.7. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|