Plan Review Notes
Plan Review Notes For Permit 01030589
Permit Number 01030589
Review Stop P
Sequence Number 1
Notes
Date Text
2001-04-02 00:00:00DENIED;
  
 1.PAGE A1 TOILET ROOM MEASUREMENTS ARE
 NOT CORRECT. FLOOR PLAN, SAME PAGE,
 BATHROOM SIZE IS 7'X7'.
  
 2.SHOW ON PLANS COMPLIANCE TO 94 SPC
 TABLE 407 MINIMUM PLUMBING FIXTURES
 REQUIRED. (NUMBER OF PEOPLE PER SHIFT)
  
 3.ONE DRINKING FOUNTAIN IS REQUIRED PER.
 TABLE 407. DRINKING FOUNTAIN SHALL
 COMPLY WITH FACBC 4.1.3(10) AND 4.15.
 PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 4.PAGE P (RISER DIAGRAM) URINAL IS UN-
 VENTED.
  
 5.FLOOR DRAIN;
 A.WHAT WILL DRAIN INTO FLOOR DRAIN
 B.SHOULD HAVE A DEEP SEAL.
 C.IS NOT VENTED SEE TABLE 908.1.
  
 6.PAGE A-2 (CABINET DETAIL) SINK TO
 COMPLY WITH FACBC 4.24.2 THRU 4.24.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377