Plan Review Notes
Plan Review Notes For Permit 01030589
Permit Number 01030589
Review Stop M
Sequence Number 1
Notes
Date Text
2001-03-23 00:00:00******************PROVISO***************
  
 NO CONDENSATE TRAP DETAIL SHOWN ON
 DRAWING M.
  
 SHALL COMPLY WITH 1997 SMC 304.8.3 -
  
 1.UNITS LARGER THAN 3 TONS (10.6KW)
 NOMINAL CAPACITY SHALL DRAIN THROUGH
 STORM DRAIN OR AN APPROVED DRY WELL.