2001-04-03 00:00:00BUILDING PLAN REVIEW
 PERMMIT# 01030589
 1041 OLD OKEECHOBEE ROAD
 ROY D. DUNWORTH CONT
 (561) 485-5210
  
 1)- PLOT PLAN DEPECTS THE PROPOSED BUILD
 ING SITUATED ON THE NORTH & WEST PROPER-
 TY LINES.THE FOOTING NOR THE DOOR SHOWN
 ON THE WEST ELEVATION CAN ENCROACH OVER
 THE PROPERTY LINE.
  
 2)_ENERGY CALCULATIONS REQUIRED, FL.
 ENERGY CODE 400.1.
  
 3)- STRUCTURAL NOTES S-1 ASSUMED SOIL
 BEARING VALUE OF 2000PSF SOILS REPORT
 REQUIRES 2500 PSF.
  
 4)- SHEET A-2 SEC. 4:
 A)- SHUTTER DETAIL NOTE "SEE ROLL-
 ADEN PRODUCT APPROVAL DWGS" FOR
 DIMENSIONS & INSTALLATION DETAIL
 THE UPPER BUCK ATTACHES TO WHAT?
 WAS THE WINDOW AND SHUTTER TEST-
 ED THIS WAY?
 B)- STEEL STAIRS: RISE & RUN, SHOP
 DRAWINGS REQUIRED, SHOW ATTACH-
 MENT TO LANDING, COLUMNS AND
 FLOOR.
 C)- SBC 104.2.2: ADD INFO, SHOW DE-
 TAIL FOR DROPPED BEAM UNDER
 STAIR STRINGER?
 D)- LINTEL SCHEDULE LIST OPENINGS
 FOR THE FIRST FLOOR BUT NOT THE
 WINDOWS OVER THE MEZANINE NOR
 THE CIRCULAR WINDOW.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 A)- SBC 1707.4 ALL GLAZED OPENINGS
 REQUIRE TESTING FORWIND PRESSURE
 A 10 SEC. LOAD EQUAL TO 1.5
 TIMES THE DESIGN LOADS.
 B)- SBC GLAZED OPENINGS REQUIRE
 LARGE MISSLE IMPACT TESTING OR
 SHUTTERS THAT HAVE PRODUCT AP-
 PROVAL, DADE COUNTY OR SBCCI RE-
 PORTS ARE ACCEPTABLE.CITY POLICY
 FOR STORM SHUTTERS REQUIRES A
 INSTALLATION PLAN & SCHEDULE.
 C)- ALL DOORS ALSO REQUIRE PRODUCT
 TESTING SBC 1606.2.6.2 (SWING &
 OVERHEAD DOORS).
 D)- 1503.3.2/1503.4.1.2: ALL ROOF
 ASSEMBLIES REQUIRE PRODUCT TEST-
 ING FOR 110 MPH.
  
 6)- A-2/ A-3 MEZANINE DECK NEEDS A
 ATTACHMENT DETAIL FOR THE FLOOR TRUSSES
 ON THE EXTERIOR WALL, TRUSS FLOOR LOAD-
 ING AS PER TABLE 1604.1 LIVE LOADS FOR
 STORAGE, LIGHT 125 PSF
 HEAVY 150 PSF
 SBC 413.4.5.2 POSTING STORAGE LOAD SIGNS
 TRUSS PLAN LAYOUT FOR MEZANINE AND ROOF.
 THE PLANS DON'T INDICATE IF THERE IS TO
 BE FLOOR TRUSSES OVER THE KITCHEN AREA,
 IF THERE IS , ISTHE NORTH KITCHEN WALL
 BEARING? IS A GIRDER REQUIREDALSO?
  
 7)- THE METAL FRAME CANOPY WILL REQUIRE
 A SEPERATE PERMIT.
  
 8)- ROOF TRUSSES: THE GABLE END MISSING
 DETAILS, DROPPED GABLE, RAKED BEAM, DE-
 TAILS ON THE ATTACHMENT OF THE GABLE
 TRUSS TO THE BEAM.
  
 9)_ MISSING ACCESS PANEL FOR THE FIRST
 FLOOR A/C UNIT.
  
 10)- MEZANINE USAGE REQUIRED, IF NOT
 USED FOR STORAGE FL. VERTICAL ACCESSI-
 BILITY BECOMES A ISSUE.
  
 11)- PLANS ARE REQUIRED TO RECEIVE
 COUNTY IMPACT FEE STAMPS BEFORE ISSUANCE
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412