Plan Review Notes
Plan Review Notes For Permit 01030568
Permit Number 01030568
Review Stop M
Sequence Number 1
Notes
Date Text
2001-03-20 00:00:00******************DENIED****************
  
 PROVIDE OUTSIDE AIR CALCULATIONS AND AIR
 BALANCE SCHEDULE AS PER ASHRAE 62-89.
  
 DRAWING M1.1 DETAIL OF ROOF PLAN HVAC
 INDICATES THE STAND FOR ACCU-1 HAVING A
 MINIMUM HEIGHT OF 12" (NOTE 3), THIS
 SHOULD BE A MINIMUM OF 18" FROM THE
 ROOF SURFACE TO BOTTOM OF THE LOWEST
 SUPPORT ON THE STAND.AMENDED 1997 SMC
 304.2.5.