Plan Review Notes
Plan Review Notes For Permit 01030568
Permit Number 01030568
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-16 00:00:001) CANVAS CANOPY TO BE FIRE RETARDANT.
 2) FIRE SPRINKLER HEADS SHOWN ON
 REFLECTED CEILING PLAN ARE TO BE DONE
 BY SEPARATE PLAN AND PERMIT.
 3) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS. THE GENERAL NOTES ON A-3
 INDICATES AND ADT FIRE ALARM SYSTEM.
 PLEASE CHECK CITY PLACE STANDARDS FOR
 FIRE ALARM EQUIPMENT AND SYSTEMS.
 4) WRONG TRAVEL DISTANCE NOTED ON PLANS.
 SHOULD READ 150 FEET INSTEAD OF 250
 FEET.