2001-03-27 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE: PLEASE SHOW LOAD CALCULATION | | PERART 220. | | PLEASE SEE 220-12 FOR TRACK LIGHTING | | CALCULATION. | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | ARE TO BE SHOWN AT 125% 215-2. | | | | 2)NOTE: PLEASE CLARIFY FEED GOING FROM | | METER TO DISCONNECT AND THEN ABACK TO | | METER AND THEN TO PANEL? METER CAN NOT | | BE USED AS A RACEWAY 373-8. TYPE-O? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|