Plan Review Notes
Plan Review Notes For Permit 01030517
Permit Number 01030517
Review Stop P
Sequence Number 4
Notes
Date Text
2001-10-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHEET P-6 AIRCHAMBERS SEC 607.8.3
 ACCESSIBLE & RECHARGEABLE, "TEMPORARY
 FIX". USE WATER HAMMER ARRESTORS AND
 SIZE AND LOCATE PER MANUFACTURE INSTALL-
 ATION INSTRUCTIONS AND WH-PDI 201. NOT
 AT TOP OF DROP BUT NEAR SOURCE (FIXTURE)
  
 2) SHEET A2.4 WATER HEATER IN A/C CLOSET
 BY KITCHENETTE AND WATER HEATER CH-2 UN-
 DER COUNTER AT SINK ON WATER RISER DIA-
 GRAM SHEET P-6. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377