Plan Review Notes For Permit 01030517 |
Permit Number |
01030517 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-10-19 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) SHEET P-6 AIRCHAMBERS SEC 607.8.3 | | ACCESSIBLE & RECHARGEABLE, "TEMPORARY | | FIX". USE WATER HAMMER ARRESTORS AND | | SIZE AND LOCATE PER MANUFACTURE INSTALL- | | ATION INSTRUCTIONS AND WH-PDI 201. NOT | | AT TOP OF DROP BUT NEAR SOURCE (FIXTURE) | | | | 2) SHEET A2.4 WATER HEATER IN A/C CLOSET | | BY KITCHENETTE AND WATER HEATER CH-2 UN- | | DER COUNTER AT SINK ON WATER RISER DIA- | | GRAM SHEET P-6. PLEASE CLAIRFY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|