Plan Review Notes
Plan Review Notes For Permit 01030517
Permit Number 01030517
Review Stop P
Sequence Number 3
Notes
Date Text
2001-09-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHEET P-6 AIR CHAMBERS SEC 607.8.3
 ACCESSIBLE AND RECHARGEABLE, "TEMPORARY
 FIX". USE WATER HAMMER ARRESTORS. SIZED
 AND LOCATED PER MANUFACTURE
 INSTALLATION INSTRUCTIONS AND WH-PDI 201
  
 2) SHEET A2.4 WATER HEATER IN A/C CLOSET
 BY KITCHENETTE AND WATER HEATER CH-2 UN-
 DER COUNTER AT SINK ON WATER RISER DIA-
 GRAM SHEET P-6. PLEASE CLARIFY.
  
 3) SHEET A2.4 & A8.1 KITCHENETTE SINK TO
 COMPLY WITH FACBC-97 SEC 4.24
  
 4) SHEET A8.1 URNAL TO COMPLY WITH FACBC
 -97 SEC 4.18.2 & 4.22.5. 17" TO LIP AFF
 AND SHOW CLEAR FLOOR SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377