Plan Review Notes For Permit 01030517 |
Permit Number |
01030517 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-09-28 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) SHEET P-6 AIR CHAMBERS SEC 607.8.3 | | ACCESSIBLE AND RECHARGEABLE, "TEMPORARY | | FIX". USE WATER HAMMER ARRESTORS. SIZED | | AND LOCATED PER MANUFACTURE | | INSTALLATION INSTRUCTIONS AND WH-PDI 201 | | | | 2) SHEET A2.4 WATER HEATER IN A/C CLOSET | | BY KITCHENETTE AND WATER HEATER CH-2 UN- | | DER COUNTER AT SINK ON WATER RISER DIA- | | GRAM SHEET P-6. PLEASE CLARIFY. | | | | 3) SHEET A2.4 & A8.1 KITCHENETTE SINK TO | | COMPLY WITH FACBC-97 SEC 4.24 | | | | 4) SHEET A8.1 URNAL TO COMPLY WITH FACBC | | -97 SEC 4.18.2 & 4.22.5. 17" TO LIP AFF | | AND SHOW CLEAR FLOOR SPACE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|