Plan Review Notes For Permit 01030517 |
Permit Number |
01030517 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-05-01 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE | | LISTED FOR FIRE PROTECTION SERVICE AND | | COMPLY WITH NFPA 24, FIRE SERVICE MAINS | | AND THEIR APPURTENANCES. | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | FOR THE INSTALLATION OF THE FIRE | | SPRINKLER SYSTEM AND FIRE PUMP ASSEMBLY. | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | FOR THE INSTALLATION OF THE FIRE ALARM | | SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND | | BATTERY CALCULATIONS ARE TO BE PROVIDED. | | 4) FIRE SPRINKLER SYSTEM AND FIRE ALARM | | SYSTEMS ARE TO BE SUPERVISED BY A | | LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 5) EMERGENCY LIGHTING REQUIRED IN | | CARD,PARTY, TV ROOM. | | 6) INGRESS AND EGRESS INTO THE COMPLEX | | SHALL BE A MINIMUM OF TWENTY FEET IN | | CLEAR WIDTH. BATTERY BACK-UP FEATURE | | SHALL BE PROVIDED FOR GATE-ARMS SHOULD | | LOSS OF POWER OCCUR. TRAFFIC CALMING | | HUMPS ARE NOT TO INTERFERE WITH FIRE | | RESCUE MOVEMENT INTO THE COMPLEX. | | 7) PLEASE INDICATE PORTABLE FIRE | | EXTINGUISHER LOCATIONS. | | 8) PLEASE EXPLAIN RATIONALE FOR THE | | SINGLE FIRE DEPARTMENT CONNECTION SHOWN | | ON THE OTHER DRAWINGS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|