2001-05-01 00:00:001) ALL UNDERGROUND FIRE MAINS ARE TO BE
 LISTED FOR FIRE PROTECTION SERVICE AND
 COMPLY WITH NFPA 24, FIRE SERVICE MAINS
 AND THEIR APPURTENANCES.
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE
 SPRINKLER SYSTEM AND FIRE PUMP ASSEMBLY.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND
 BATTERY CALCULATIONS ARE TO BE PROVIDED.
 4) FIRE SPRINKLER SYSTEM AND FIRE ALARM
 SYSTEMS ARE TO BE SUPERVISED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 5) EMERGENCY LIGHTING REQUIRED IN
 CARD,PARTY, TV ROOM.
 6) INGRESS AND EGRESS INTO THE COMPLEX
 SHALL BE A MINIMUM OF TWENTY FEET IN
 CLEAR WIDTH. BATTERY BACK-UP FEATURE
 SHALL BE PROVIDED FOR GATE-ARMS SHOULD
 LOSS OF POWER OCCUR. TRAFFIC CALMING
 HUMPS ARE NOT TO INTERFERE WITH FIRE
 RESCUE MOVEMENT INTO THE COMPLEX.
 7) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
 8) PLEASE EXPLAIN RATIONALE FOR THE
 SINGLE FIRE DEPARTMENT CONNECTION SHOWN
 ON THE OTHER DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910