2001-04-06 00:00:00 | DENIED; |
| |
| 1.(GENERAL NOTES) #15. COPIES OF ALL |
| DOCUMENTS TO BE FILED WITH THE |
| DEPARTMENT OF CONSTRUCTION SERVICES. |
| CHANGE "A" TO CITY OF WEST PALM BEACH. |
| "L" SAME AS "A". |
| |
| 2.BACKFLOW PREVENTERS SHALL BE INSTALLED |
| AT EACH BUILDING. |
| |
| 3.(SEWAGE COLLECTION SYSTEM) NOTE 8. |
| TWO COATS SHALL BE APPLIED TO THE OUT |
| SIDE. |
| |
| 4.(WATER DISTRIBUTION SYSTEM) NOTE 3 |
| CITY OF WEST PAKM BEACH NOT SUNRISE. |
| |
| 5.WATER HAMMER ARRESTERS TO COMPLY WITH |
| 607.8.1, 607.8.2 AND 608.8.3 |
| |
| 6.PAGE P-3 WASTE RISER S3 AND S4. THREE |
| INCH. STACK MAXIMUM LENTH IS 50 FT. |
| FROM THE HOUSE DRAIN THRU THE ROOF. |
| SPC 911.4 AND TABLE 911.4. |
| |
| 7.PAGE P-6 FLOOR DRAINS IN PUBLIC REST- |
| ROOMS SHALL HAVE TRAP PRIMERS.FLOOR |
| DRAINS IN LAUNDRY ROOM SHALL BE DEEP |
| SEAL. SEC. 409.4.1.1 AND 409.4.1.4. |
| |
| 8.PAGE A8.1 SHOW MEASURMENTS FOR TOILET |
| LOCATION. SHOW THE 18"SIDE TO COMPLY |
| WITH THE FHA. |
| |
| 9.WHAT HIGHT ABOVE THE ROOF ARE THE |
| OVERFLOW DRAINS SET ABOVE THE ROOF? |
| |
| 10.SHOW NUMBER OF UNITS IN EACH BUILDING |
| THAT WILL BE FURNISHED WITH GRAB BARS |
| AND HANDICAP ACCESSORIES. |
| |