2001-04-06 00:00:00DENIED;
  
 1.(GENERAL NOTES) #15. COPIES OF ALL
 DOCUMENTS TO BE FILED WITH THE
 DEPARTMENT OF CONSTRUCTION SERVICES.
 CHANGE "A" TO CITY OF WEST PALM BEACH.
 "L" SAME AS "A".
  
 2.BACKFLOW PREVENTERS SHALL BE INSTALLED
 AT EACH BUILDING.
  
 3.(SEWAGE COLLECTION SYSTEM) NOTE 8.
 TWO COATS SHALL BE APPLIED TO THE OUT
 SIDE.
  
 4.(WATER DISTRIBUTION SYSTEM) NOTE 3
 CITY OF WEST PAKM BEACH NOT SUNRISE.
  
 5.WATER HAMMER ARRESTERS TO COMPLY WITH
 607.8.1, 607.8.2 AND 608.8.3
  
 6.PAGE P-3 WASTE RISER S3 AND S4. THREE
 INCH. STACK MAXIMUM LENTH IS 50 FT.
 FROM THE HOUSE DRAIN THRU THE ROOF.
 SPC 911.4 AND TABLE 911.4.
  
 7.PAGE P-6 FLOOR DRAINS IN PUBLIC REST-
 ROOMS SHALL HAVE TRAP PRIMERS.FLOOR
 DRAINS IN LAUNDRY ROOM SHALL BE DEEP
 SEAL. SEC. 409.4.1.1 AND 409.4.1.4.
  
 8.PAGE A8.1 SHOW MEASURMENTS FOR TOILET
 LOCATION. SHOW THE 18"SIDE TO COMPLY
 WITH THE FHA.
  
 9.WHAT HIGHT ABOVE THE ROOF ARE THE
 OVERFLOW DRAINS SET ABOVE THE ROOF?
  
 10.SHOW NUMBER OF UNITS IN EACH BUILDING
 THAT WILL BE FURNISHED WITH GRAB BARS
 AND HANDICAP ACCESSORIES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377