2001-03-14 00:00:00 | 1) PLEASE INDICATE FIRE RESCUE ACCESS |
| INTO THE APARTMENT COMPLEX. THE OPENING |
| THAT FIRE RESCUE IS EXPECTED TO PASS |
| THRU MUST BE AT LEAST 20 FEET IN CLEAR |
| WIDTH. HOW DOES FIRE RESCUE EQUIPMENT |
| PASS THE SECURITY FEATURES PLANNED FOR |
| THE COMPLEX DRIVE OPENINGS. |
| 2) UNDERGROUND FIRE LINES, FIRE HYDRANTS |
| AND APPURTENACES TO COMPLY WITH NFPA 24. |
| THIS EQUIPMENT TO MEET UTILITY AND FIRE |
| RESCUE STANDARDS. WET FIRE HYDRANTS ARE |
| TO BE PROVIDED PRIOR TO, DURING AND |
| AFTER CONSTRUCTION. |
| 3) PLEASE INDICATE IF GATES OR FRAME |
| ARMS WILL BE PROVIDED FOR SECURITY |
| PURPOSES. |
| 4) BUILDING ADDRESSES REQUIRED PER CITY |
| CODE REQUIREMENTS. |
| 5) CLUBHOUSE TO PROVIDE PROVISIONS FOR |
| AT LEAST TWO HANDICAPPED PERSONS. |
| 6) PLEASE INDICATE HOW THE DRYER CHASE |
| CAN BE CLEANED OF COMBUSTIBLE LINT |
| BUILD-UP. PLEASE PROVIDE UL NUMBERS FOR |
| ALL SHAFTS. |
| 7) NO HYDRAULIC CALCULATIONS PROVIDED |
| WITH FIRE SPRINKLER DRAWINGS. ALL |
| BUILDINGS ARE TO BE COMPLETELY FIRE |
| SPRINKLER PROTECTED. ALL ELECTRICAL, |
| MECHANICAL AND SERVICE ROOMS ARE TO BE |
| PROTECTED WITH FIRE SPRINKLER HEADS. |
| ALSO ALL VERTICAL SHAFTS ARE TO BE |
| FIRE SPRINKLER PROTECTED. |
| 8) EMERGENCY LIGHTING REQUIRED IN FIRE |
| PUMP ROOM. OKAY, LOCATED ON PLANS. |
| 9) ALL BUILDINGS THREE STORIES OR MORE |
| AND 50 FEET IN HEIGHT MUST HAVE |
| STANDPIPE SYSTEMS IN ACCORDANCE WITH |
| NFPA 14. |
| 10) HANDRAILS AND GUARDS TO COMPLY WITH |
| NFPA 101, THE LIFE SAFETY CODE, 1985 |
| EDITION. |
| 11) MORE DETAILS NEEDED FOR FIRE PUMP |
| EQUIPMENT AND APPURTENANCES. |
| 12) IS ACCESS PROVIDED INTO THE WOOD |
| TRUSS AREA. |
| 13) TENANT SEPARATIONS TO COMPLY WITH |
| BUILDING CODE REQUIREMENTS. |
| 14) PLEASE BE ADVISED OF THE STRETCHER |
| REQUIREMENTS OF THE STANDARD BUILDING |
| CODE, SECTION 3003.4 FOR BUILDINGS FOUR |
| OR MORE FLOORS. |
| 15) PLEASE PROVIDE INTERIOR FINISH |
| CLASSIFICATION INFORMATION. |
| 16) IS BATTERY BACK-UP PLANNED FOR THE |
| SECURITY FEATURES AT THE ENTRANCE SHOULD |
| LOSS OF POWER RESULT. |
| 17) DOES THE NOTE ON PAGE E12 MEAN |
| ONLY A SINGLE FIRE ALARM PANEL FOR THE |
| COMPLEX. WHAT HAPPENS WHEN THIS PANEL |
| IS DOWN FOR REPAIRS OR REPLACEMENT. |
| |
| CAPTAIN MIKE CARSILLO |
| 659-8096,EXT.8497 |
| 835-2910 |