Plan Review Notes
Plan Review Notes For Permit 01030517
Permit Number 01030517
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-14 00:00:001) PLEASE INDICATE FIRE RESCUE ACCESS
 INTO THE APARTMENT COMPLEX. THE OPENING
 THAT FIRE RESCUE IS EXPECTED TO PASS
 THRU MUST BE AT LEAST 20 FEET IN CLEAR
 WIDTH. HOW DOES FIRE RESCUE EQUIPMENT
 PASS THE SECURITY FEATURES PLANNED FOR
 THE COMPLEX DRIVE OPENINGS.
 2) UNDERGROUND FIRE LINES, FIRE HYDRANTS
 AND APPURTENACES TO COMPLY WITH NFPA 24.
 THIS EQUIPMENT TO MEET UTILITY AND FIRE
 RESCUE STANDARDS. WET FIRE HYDRANTS ARE
 TO BE PROVIDED PRIOR TO, DURING AND
 AFTER CONSTRUCTION.
 3) PLEASE INDICATE IF GATES OR FRAME
 ARMS WILL BE PROVIDED FOR SECURITY
 PURPOSES.
 4) BUILDING ADDRESSES REQUIRED PER CITY
 CODE REQUIREMENTS.
 5) CLUBHOUSE TO PROVIDE PROVISIONS FOR
 AT LEAST TWO HANDICAPPED PERSONS.
 6) PLEASE INDICATE HOW THE DRYER CHASE
 CAN BE CLEANED OF COMBUSTIBLE LINT
 BUILD-UP. PLEASE PROVIDE UL NUMBERS FOR
 ALL SHAFTS.
 7) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS. ALL
 BUILDINGS ARE TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. ALL ELECTRICAL,
 MECHANICAL AND SERVICE ROOMS ARE TO BE
 PROTECTED WITH FIRE SPRINKLER HEADS.
 ALSO ALL VERTICAL SHAFTS ARE TO BE
 FIRE SPRINKLER PROTECTED.
 8) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM. OKAY, LOCATED ON PLANS.
 9) ALL BUILDINGS THREE STORIES OR MORE
 AND 50 FEET IN HEIGHT MUST HAVE
 STANDPIPE SYSTEMS IN ACCORDANCE WITH
 NFPA 14.
 10) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 11) MORE DETAILS NEEDED FOR FIRE PUMP
 EQUIPMENT AND APPURTENANCES.
 12) IS ACCESS PROVIDED INTO THE WOOD
 TRUSS AREA.
 13) TENANT SEPARATIONS TO COMPLY WITH
 BUILDING CODE REQUIREMENTS.
 14) PLEASE BE ADVISED OF THE STRETCHER
 REQUIREMENTS OF THE STANDARD BUILDING
 CODE, SECTION 3003.4 FOR BUILDINGS FOUR
 OR MORE FLOORS.
 15) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 16) IS BATTERY BACK-UP PLANNED FOR THE
 SECURITY FEATURES AT THE ENTRANCE SHOULD
 LOSS OF POWER RESULT.
 17) DOES THE NOTE ON PAGE E12 MEAN
 ONLY A SINGLE FIRE ALARM PANEL FOR THE
 COMPLEX. WHAT HAPPENS WHEN THIS PANEL
 IS DOWN FOR REPAIRS OR REPLACEMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910