Plan Review Notes For Permit 01030444 |
Permit Number |
01030444 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-13 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | TO BE A MINIMUM OF THREE FEET FROM | | AIR CONDITONER DIFFUSERS. | | 2) DUCT SMOKE DETECTORS WHEN ACTIVATED | | ARE TO SHUT DOWN AIR HANDLING DEVICES | | AND ACTIVATE THE FIRE ALARM SYSTEM. | | 3) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | IS TO BE AUDIBLE THROUGHOUT THE | | BUILDING. | | 4) FIRE ALARM SYSTEM TO BE CLASS A OR | | FULLY ADDRESSABLE. | | 5) FIRE ALARM SYSTEM IS TO BE MONITORED | | BY A LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 6) HEAT DETECTORS ASSOCIATED WITH THE | | ELEVATOR(S) ARE TO SHUNT TRIP AND NOT | | BE CONNECTED TO THE FIRE ALARM SYSTEM. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|