Plan Review Notes
Plan Review Notes For Permit 01030429
Permit Number 01030429
Review Stop B
Sequence Number 1
Notes
Date Text
2001-03-29 00:00:00PROVISO: 03/29/01
 1)- SBC 1707.4 EXTERIOR DOOR & WINDOW
 ASSEMBLIES: ALL GLAZED OPENINGS REQUIRE
 TESTING FOR A PERIOD OF TIME OF 10
 SECOND PERIOD AT A LOAD EQUAL TO 1.5
 TIMES THE DESIGN PRESSURE. MISSING
 REPORTS:
 A)- FIXED WINDOWS
 B)- MULLIONS
 C)- SLIDING WINDOWS
 D)- FRENCH DOORS
 2)- SBC 1707.4.1- STORM SHUTTERS REQUIRE
 A KEY PLAN WITH A FASTENING SCHEDULE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659 -8096 EX 8412