Plan Review Notes
Plan Review Notes For Permit 01030376
Permit Number 01030376
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-11 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 THIS IS INFORMATION NEEDED FOR ALL PLANS
 WHEN CHANGING/ INSTALLING NEW EQUIPMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  