2001-03-11 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: NO WIRE SIZES ON RISER DIAGRAM?
 CONDUIT SIZE? GROUND SIZE? COLD WATER?
  
  
 3)NOTE: SHOW ALL MEANS OF EGRESS LIGHTIN
 G AND ALL SWITH LEGS FOR CONTROLL.
 210-70.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372