Plan Review Notes
Plan Review Notes For Permit 01030213
Permit Number 01030213
Review Stop P
Sequence Number 1
Notes
Date Text
2001-04-11 00:00:00REVIEW NOTES:
 PLUMBING PLAN REVIEW DENIED.
 REFERENCES STD PLBG CODE-94 FACBC-97
 (1) CONTACT DEPT. OF BUSINESS
 REGULATION, HOTEL &RESTURANT DIVISION
 PRIOR TO PLUMBING PLAN REVIEW FOR THEIR
 COMMENTS & REVIEW. (954) 958-5520
  
 (2) PAGE A-4 ELEVATIONS #6 & #7 URNAL
 LIP TO 17" AFF. FACBC-97 4.18.2
  
 (3) PAGE P-1 PLMG NOTE # 5
 AIR CHAMBERS TO BE ACCESSABLE AND
 RECHARGABLE. SPC-94 607.8.3
  
 (4) NOTE; GREASE TRAP TO BE SIZED BY
 RODNEY COMPO OF THE WPB UTILITY DEPT.
 (561) 837-4074
  
 (5) TWO INCH VENT FORM GREASE TRAP
 NOT REQUIRED. 3" VENT WILL BE
 EXCEPTABLE.
  
 (6) PAGE P-3 DISHWASHER SHALL DISCHARGE
 INTO SANITARY NOT GREASE.
  
 (7) PAGE P-3 SANITARY AND GREASE LINES
 SHALL HAVE 2-WAY CLEAN-OUTS AT SEWER
 CONNECTIONS WITH-IN 3' OF BLDG.
  
 (8) PAGE P-3NO RECEPTICAL FOR ICE
 MACHINE TO DRAIN INTO.
  
 (9) PAGES P-4 & P-5 SHOWES 140 DEGREE
 HAT WATER TO SS-1 HAND SINK. THIS IS
 NOT ACCEPTABLE.
  
 (10) PAGE P-5 WASTE & VENT PIPING
 DIAGRAM SHOWS HORIZONTAL DRY VENT.
 HORIZONTAL DRY VENTS NOT ALLOWED
 SPC-94 914.2
  
 (11) PAGE P-6 WATER HEATER DETAIL:
 RELIEF DRAIN LINE TO DISCHARGE OUTSIDE
 OF BLDG. IN AN OBSERVABLE LOCATON.
 SPC-94 507.8.4
  
 (12) WOMEN'S AND MEN'S HDCP STALLS DOOR
 SWINGS INTO CLEAR FLOOR SPACE OF LAVS.
  
 (13) ONE URNAL TO BE TO HDCP SPECS
 WITH AN ELONGATED RIM.
  
 (14) SOLENOID VALVE SHALL BE MOUNTED
 BELOW THE CEILING NEXT TO COOKING
 EQUIPMENT WITH SHUTOFF VALVE UP-STREAM
 OF UNION AND SOLENOID VALVE.
  
 (15) PAGE P-6 GAS RISER SAFTY RELIEF
 VALVE NOT REQUIRED.
  
 (16) GAS WILL BE ON SEPARATE PERMIT.
 GAS PERMIT APPLICATION REQUIREMENTS OF
 JULY 12, 2000 TO BE SUBMITTED.
 END OF COMMETS. CONTACT KEN STEVENS
 FOR ANY QUESTIONS. (561) 659-8096 X 8389
 AND X 8377