2001-04-11 00:00:00 | REVIEW NOTES: |
| PLUMBING PLAN REVIEW DENIED. |
| REFERENCES STD PLBG CODE-94 FACBC-97 |
| (1) CONTACT DEPT. OF BUSINESS |
| REGULATION, HOTEL &RESTURANT DIVISION |
| PRIOR TO PLUMBING PLAN REVIEW FOR THEIR |
| COMMENTS & REVIEW. (954) 958-5520 |
| |
| (2) PAGE A-4 ELEVATIONS #6 & #7 URNAL |
| LIP TO 17" AFF. FACBC-97 4.18.2 |
| |
| (3) PAGE P-1 PLMG NOTE # 5 |
| AIR CHAMBERS TO BE ACCESSABLE AND |
| RECHARGABLE. SPC-94 607.8.3 |
| |
| (4) NOTE; GREASE TRAP TO BE SIZED BY |
| RODNEY COMPO OF THE WPB UTILITY DEPT. |
| (561) 837-4074 |
| |
| (5) TWO INCH VENT FORM GREASE TRAP |
| NOT REQUIRED. 3" VENT WILL BE |
| EXCEPTABLE. |
| |
| (6) PAGE P-3 DISHWASHER SHALL DISCHARGE |
| INTO SANITARY NOT GREASE. |
| |
| (7) PAGE P-3 SANITARY AND GREASE LINES |
| SHALL HAVE 2-WAY CLEAN-OUTS AT SEWER |
| CONNECTIONS WITH-IN 3' OF BLDG. |
| |
| (8) PAGE P-3NO RECEPTICAL FOR ICE |
| MACHINE TO DRAIN INTO. |
| |
| (9) PAGES P-4 & P-5 SHOWES 140 DEGREE |
| HAT WATER TO SS-1 HAND SINK. THIS IS |
| NOT ACCEPTABLE. |
| |
| (10) PAGE P-5 WASTE & VENT PIPING |
| DIAGRAM SHOWS HORIZONTAL DRY VENT. |
| HORIZONTAL DRY VENTS NOT ALLOWED |
| SPC-94 914.2 |
| |
| (11) PAGE P-6 WATER HEATER DETAIL: |
| RELIEF DRAIN LINE TO DISCHARGE OUTSIDE |
| OF BLDG. IN AN OBSERVABLE LOCATON. |
| SPC-94 507.8.4 |
| |
| (12) WOMEN'S AND MEN'S HDCP STALLS DOOR |
| SWINGS INTO CLEAR FLOOR SPACE OF LAVS. |
| |
| (13) ONE URNAL TO BE TO HDCP SPECS |
| WITH AN ELONGATED RIM. |
| |
| (14) SOLENOID VALVE SHALL BE MOUNTED |
| BELOW THE CEILING NEXT TO COOKING |
| EQUIPMENT WITH SHUTOFF VALVE UP-STREAM |
| OF UNION AND SOLENOID VALVE. |
| |
| (15) PAGE P-6 GAS RISER SAFTY RELIEF |
| VALVE NOT REQUIRED. |
| |
| (16) GAS WILL BE ON SEPARATE PERMIT. |
| GAS PERMIT APPLICATION REQUIREMENTS OF |
| JULY 12, 2000 TO BE SUBMITTED. |
| END OF COMMETS. CONTACT KEN STEVENS |