Plan Review Notes
Plan Review Notes For Permit 01030213
Permit Number 01030213
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-02 00:00:00BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412
  
 1)- TABLE 600 EXT. BEARING WALL 3'/10'
 ALLOWABLE OPENINGS IN WALL 10%. NEED TO
 REDUCE OPENING BY 63.82 SQ. FT.
  
 13.8750'X 65'= 901.88 SQ. FT
 901.88 S.F. X 10%= 90.18 SQ. FT.
  
 OPENING:
 14' X 11"= 154'
 154'- 90.18'= 63.82'
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412