Plan Review Notes For Permit 01030086 |
Permit Number |
01030086 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-05 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | TO BE A MINIMUM OF THREE FEET FROM | | AIR CONDITONER DIFFUSERS. | | 2) HOOD EXTINGUISHING SYSTEMS ARE TO | | BE TIED INTO FIRE ALARM SYSTEM. | | 3) FIRE ALARM SYSTEM TO BE MONITORED BY | | A LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 4) AFTER INSTALLATION, SYSTEM TO BE | | TESTED WITH FIRE RESCUE PERSONNEL. | | 5) SYSTEM TO BE CLASS A OR FULLY | | ADDRESSABLE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|