2001-03-05 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE
 TO BE A MINIMUM OF THREE FEET FROM
 AIR CONDITONER DIFFUSERS.
 2) HOOD EXTINGUISHING SYSTEMS ARE TO
 BE TIED INTO FIRE ALARM SYSTEM.
 3) FIRE ALARM SYSTEM TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 4) AFTER INSTALLATION, SYSTEM TO BE
 TESTED WITH FIRE RESCUE PERSONNEL.
 5) SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
  