2001-03-23 00:00:00CHECKLIST:
  
 1-NOTICE OF COMMENCEMENT IS INCOMPLETE.
 IT DOESN'T HAVE ANY INFORMATION
 REGARDING THE GENERAL DESCRIPTION OF
 IMPROVEMENTS.
 2-ARCHITECT TO REVISE THE DESIGN
 CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. SEE COMMENTS ON FORM.
 AND, SIGN, SEAL AND DATE FORM AS
 REQUIRED BY CHAPTER 481 FL. STATUTES.
 3-ARCHITECT TO SIGN, SEAL AND DATE THE
 ENERGY CALCULATIONS AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 4-CLARIFY HOW IS WATER RUNNING OUT OF
 THE NEW ROOF. IS THERE ANY ROOF DRAIN.
 SCUPPERS ARE SECONDARY DRAINAGE.
 5-PROVIDE COMPLETE INFORMATION FOR:
 -CONNECTION OF STEEL COLUMN AT BASE.
 -CONNECTION OF FLOOR JOISTS AND ROOF
 RAFTERS AT BOTH ENDS.
 -SPECIFY PLYWOOD SHEATHING FASTENING AS
 PER SEC 2306 CITY AMENDMENTS TO SBC/97
 6-SPECIFY THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 7-PROVIDE TWO COPIES OF CURRENT SBCCI OR
 DADE COUNTY APPROVAL FOR:
 -FLAT ROOF SYSTEM.
 -EXTERIOR DOORS AND WINDOWS (ONLY ONE
 COPY WAS SUBMITTED).
 8-PROVIDE INSTALLATION DETAILS OF IRON
 RAILING. SEC 1608.2 SBC 1997.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.