2002-07-08 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) SHT P4.2 3" PLANTER DRAIN SHOWN ON
 FLAT DRAWING P1.0 MISSING FROM STORM
 RISER DIAGRAM.
 2) SHT P1.2A REVISION SHOWS NO PIPING TO
 ROOF DRAINS, 1 NEW 4" RD-A, 2" SCUPPER
 DRAINS COL. LINE X15, 3" & 4" SCUPPER
 DRAINS COL. LINE BELOW X26. PLEASE
 CLAIRFY. ARE ORIGINAL ROOF DRAINS STILL
 BEING USED? ARE SCUPPERS SECONDARY
 DRAINS? IF SO THEY CAN NOT TIE INTO
 PRIMARY DRAIN SYSTEM. NO SECONDARY DRAIN
 SHOWN FOR LOWER ROOF TO THE LEFT SIDE.
 3) PLEASE INDICATE WHERE ALL SECONDARY
 ROOF DRAINS DRAIN TO.
 4) SHT P4.1 GREASE INTERCEPTOR DETAIL,
 2 WAY CLEAN OUTS ARE REQUIRED FOR INLET
 & OUTLET SIDES OF GREASE INTERCEPTOR.
 5) SHT P4.2 RAINWATER RISER DIAGRAM, THE
 AREA IN QUESTION ON COMMENT #2, (SHT P1.
 2), IS NOT SHOWN ON RAINWATER RISER DIA-
 GRAM. PLEASE INDICATE WHERE THIS IS LO-
 CATED ON RISER DIAGRAM.
 6) SHT P4.4 FUNNEL FLOOR DRAINS ARE NOT
 APPROVED. ALL INDIRECT WASTE SHALL DRAIN
 INTO A FLOOR SINK. PLEASE DELETE AND
 SHOW FLOOR SINKS.
 7) SHT P4.5 SANT RISER DIAGRAM. PLEASE
 SHOW FIXTURE UNITS DRAINING IN SYSTEM.
 SHOW TOTAL AMOUNT AND SHOW DFU'S AS THEY
 ACCUMULATE IN SYSTEM.
  