Plan Review Notes
Plan Review Notes For Permit 01021024
Permit Number 01021024
Review Stop P
Sequence Number 2
Notes
Date Text
2001-06-04 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) PREVIOUS COMMENTS NOT ADDRESSED
 SHT A1.1, A1.8,DOOR SWINGS INTO CLEAR
 FLR SPACE OF LAV, RM # 305,SEC 4.17.5
 (2) SHT P1.0,P4.1 GREASE TRAP SIZE AND
 TYPE TO BE REVIEWED BY WPB,RSTP ENVIRO-
 MENTAL COMPLIANCE RODNEY COMPO 561-837-
 4074.WITH CUT SHTS FROM MFG.
 (3) SHT A6.13 ELEVATIONS,DIMENSIONS OF
 H/C PLUMBING FIXTURES INCLUDING URINALS,
 (4) SHT P1.1B CHILLER PLANT,REST RM #132
 SHOWER COMPARTMENT,TO COMPLY W/FACBC 97
 SEC 4.21, FIG. 35 A OR B.
 (5) SHT P3.1 PROVIDE A LIST OF KITCHEN
 EQUIPMENT FOR PLUMBING,GAS FIXTURES,
 SPC 94 SEC 104.3
 (6) SHT P4.1 DISHWASHER TO BY PASS G/W,
 CONNECT TO SANITARY SEWER, LOCAL ORD.
 #2938-96 WPB,RSTP.
 (7) SHT P4.1 PROVIDE A COMPLETE GAS
 ISOMETRIC,FROM THE METER TO THE FARTHEST
 POINT OF USE,INCLUDE BOILER & KITCHEN.
 SEE ATTACHED GAS PERMIT APPLICATION REQ-
 UIRMENTS,SGC 97 SEC 104.3 ADDRESS EACH
 OF NINE ITEMS.
 (8) SHT P4.2 SHOW CALCULATIONS FOR ROOF
 & SCUPPER DRAINS, INCLUDING VERTICAL
 WALLS,ALSO SECONDARY DRAINS FROM ABOVE
 DRAINING ON TO LOWER ROOFS.SPC 94
 SEC 1101.2,1108.3,1109.1
 (9) SHTP4.1 SPC 94 SEC 921.4 GEN. DESIGN
 HORIZONTAL WASTE & VENT SYSTEM, EACH F/S
 BRANCH TO CONNECT SEPERATELY TO MAIN
 VENTED LINE, MIN SIZE 3".
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X8233