Plan Review Notes For Permit 01021024 |
Permit Number |
01021024 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-06-06 00:00:00 | *******************DENIED*************** | | | | 1.PLEASE PROVIDE O. A. CALCULATIONS | | AS PER ASHRAE 62-89. | | | | 2.PROVIDE AIR BALANCE SCHEDULE FOR | | COMPLIANCE WITH 1997 SMC 501.2. | | | | 3.PROVIDE INFORMATION SHOWING | | COMPLIANCE WITH 1997 SMC CHAPTER | | 11, LEVEL 1 MACHINE ROOM, I.E. | | SIGNAGE, LOCATION OF HORN & STROBES | | (OUTSIDE & INSIDE ROOM), LOCATION | | OF REFRIGERANT SENSORS & BREATHING | | APPARATUS. | | | | 4.DRAWING H1.3 "REFER TO MATCH LINE | | H1.4A", NO SUCH DRAWING WITH THIS | | SET OF PLANS. | | | | 5.DUCT SMOKE DETECTORS NEED TO BE | | INDICATED ON PLAN. | | | | 6.ADDITIONAL MECH PERMIT & PLANS | | REQUIRED FOR FUEL (PIPING & TANK). | | | | 7.ADDITIONAL MECH PERMIT & PLANS | | REQUIRED FOR KITCHEN HOOD & | | DUCTWORK. | | | | NOTE:PRIOR TO CONNECTING TO ANY | | EXISTING DUCTWORK, CALL FOR AN | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096EXT. 8388. |
|