Plan Review Notes
Plan Review Notes For Permit 01021024
Permit Number 01021024
Review Stop E
Sequence Number 2
Notes
Date Text
2001-06-08 00:00:00**************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE IN REFERENCE TO
 THE SHUNT TRIP BEING SHOWN FOR MAIN
 BUILDING POWER SHUT OFF.
 PLEASE SEE 230-72,230-76,230-79
 THE GROUPING OF DISCONNECTING SERVICES
 NEEDS TO BE IN SAME AREAS.
  
 2)NOTE: PLEASE SEE E4-1 DISTRIBUTION
 LOAD SUNMMARY IS BLANK? PLEASE CLARIFY.
  
 3)NOTE: PLEASE NOTE THAT UNDER F.S.
 AND'F.A.C 471.025 AND 481.221, ALL
 PLANSDONE BY ARCHS/ENGINEERS NEED TO BE
 SIGNED, SEALED AND DATED.
  
 3)NOTE: PLEASE NOTE THAT PLANS ARE IN
 VERY GOOD SHAPE. IT HAS BEEN ACCEPTED TH
 AT A SHUNT MEANS FOR"SHUTTING DOWN"
 EMERGENCY GENERATORS IS OK AS LONG A
 MANUAL MEANS OF DISCONNECT IS ALSO
 THERE ON THE EQUIPMENT. 230-76 AND -79.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372