2001-06-08 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE:PLEASE NOTE IN REFERENCE TO | | THE SHUNT TRIP BEING SHOWN FOR MAIN | | BUILDING POWER SHUT OFF. | | PLEASE SEE 230-72,230-76,230-79 | | THE GROUPING OF DISCONNECTING SERVICES | | NEEDS TO BE IN SAME AREAS. | | | | 2)NOTE: PLEASE SEE E4-1 DISTRIBUTION | | LOAD SUNMMARY IS BLANK? PLEASE CLARIFY. | | | | 3)NOTE: PLEASE NOTE THAT UNDER F.S. | | AND'F.A.C 471.025 AND 481.221, ALL | | PLANSDONE BY ARCHS/ENGINEERS NEED TO BE | | SIGNED, SEALED AND DATED. | | | | 3)NOTE: PLEASE NOTE THAT PLANS ARE IN | | VERY GOOD SHAPE. IT HAS BEEN ACCEPTED TH | | AT A SHUNT MEANS FOR"SHUTTING DOWN" | | EMERGENCY GENERATORS IS OK AS LONG A | | MANUAL MEANS OF DISCONNECT IS ALSO | | THERE ON THE EQUIPMENT. 230-76 AND -79. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|