Plan Review Notes For Permit 01021024 |
Permit Number |
01021024 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-06-18 00:00:00 | SHEET H8.4SMOKE CONTROL SEQUENCEDOES | | NOT APPEAR TO ADDRESS THE REQUIEMENTS | | OF SBC 414.8 FOR OTHER OCCUPIED SPACES | | SUCH AS THE VARIOUS GALLERIES ON ALL | | THREE FLOORS. | | | | WILL THE ATRIUM BEUNDER POSITIVE OR | | NEGATIVE PRESSURE DURING SMOKE REMOVAL | | OPERATIONS?HAS THE EFFECT ON | | OPERATION OF THE TWO STAIR SHAFT DOORS | | BEEN ANALYZED UNDERBOTH | | +/- PRESSURES. | | | | | | | | PROVIDE ACCEPTANCE REPPORTS AND TEST | | DATA FOR THE DOORS WINDOWS AND ROOF | | COVERINGS.INCLUDE METHOD OF HURRICANE | | MISSILEIMPACT RESISTANCE. |
|