Plan Review Notes
Plan Review Notes For Permit 01021024
Permit Number 01021024
Review Stop B
Sequence Number 2
Notes
Date Text
2001-06-18 00:00:00SHEET H8.4SMOKE CONTROL SEQUENCEDOES
 NOT APPEAR TO ADDRESS THE REQUIEMENTS
 OF SBC 414.8 FOR OTHER OCCUPIED SPACES
 SUCH AS THE VARIOUS GALLERIES ON ALL
 THREE FLOORS.
  
 WILL THE ATRIUM BEUNDER POSITIVE OR
 NEGATIVE PRESSURE DURING SMOKE REMOVAL
 OPERATIONS?HAS THE EFFECT ON
 OPERATION OF THE TWO STAIR SHAFT DOORS
 BEEN ANALYZED UNDERBOTH
 +/- PRESSURES.
  
  
  
 PROVIDE ACCEPTANCE REPPORTS AND TEST
 DATA FOR THE DOORS WINDOWS AND ROOF
 COVERINGS.INCLUDE METHOD OF HURRICANE
 MISSILEIMPACT RESISTANCE.