Plan Review Notes For Permit 01021024 |
Permit Number |
01021024 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-19 00:00:00 | DENIED; | | | | 1.A1.1 (119) WOMENS ROOM HANDICAP STALL. | | DOOR CANNOT SWING INTO CLEAR FLOOR | | SPACE OF LAV. ALSO ROOM (305) | | | | 2.GREASE TRAP SIZE AND LOCATION TO BE | | APPROVED BY RODNEY COMPO OF THE UTILTY | | DEPARTMENT. 835-7423 | | | | 3.SHOW ARCHITECTURAL DRAWINGS OF | | HANDICAP STALLS AND HANDICAP URINALS | | SHOWING SIZES TO COMPLY WITH THE 97 | | FACBC. | | | | 4.RISER DIAGRAMS REQUIRED FOR WATER, | | SANITARY, RAIN WATER AND GAS. | | | | 5.NEED ARCHITECTURAL DRAWING OF BOILERS. | | SHOW PIPE INSTALLATION. | | | | 6.MORE INFOMATION REQUIRED FOR GAS; | | A.TYPE OF GAS. | | B.DELIVERY PRESSURE. | | C.TYPE OF PIPE AND HOW IT WILL BE | | INSTALLED. | | D.BTU LOAD FOR EACH APPLIANCE AND | | TOTAL BTU LOAD ON SYSTEM. | | E.DISTANCE TO MOST REMOTE OUTLET. | | F.CALCULATIONS FOR COMBUSTION AIR FOR | | BOILERS. | | G.SHOW GAS VENTS FOR BOILERS. | | | | 7.SITE DRAWINGS DO NOT SHOW TIE IN FOR | | RAIN LEADERS. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|