Date |
Text |
2001-03-01 00:00:00 | 1) PLEASE INDICATE PROPOSED FIRE RESCUE |
| INGRESS AND EGRESS POINTS TO THE NEW |
| ADDITION. |
| 2) PLEASE LOCATE EXISTING FIRE HYDRANT |
| LOCATIONS FOR MUSEUM. |
| 3) PLEASE PROVIDE MORE DETAILS ON GATES |
| LOCATED NEAR SOUTH DIXIE FOR DROP OFF |
| LANE. |
| 4) PROVISIONS ARE TO BE MADE FOR AT |
| LEAST TWO HANDICAPPED PERSONS. |
| 5) MAXIMUM TRAVEL DISTANCE NOTE ON CD1.1 |
| IS INCORRECT. MAXIMUM TRAVEL DISTANCE |
| IN SPRINKLERED BUILDINGS OF THIS TYPE IS |
| 200 FEET. |
| 6) PLEASE FURTHER CLARIFY CD1.1. EXIT |
| SIGNS AND DOORS MUST BE SHOWN. PLAN WAS |
| DIFFICULT TO FOLLOW. |
| 7) PLEASE ADVISE HOW DEMOLITION WILL |
| OCCUR WHEN THE MUSEUM IS OPEN. |
| 8) PLEASE PROVIDE PRODUCT APPROVAL FOR |
| ONE HOUR FIRE RATED GLAZING IN CORRIDOR |
| 101. |
| 9) PLEASE INDICATE HOW ILLUMINATED |
| EXIT SIGNS WILL BE INSTALLED IN OFFICES |
| 230 DUE TO HEADROOM ISSUES. |
| 10) PLEASE PROVIDE MORE DETAILS ON |
| EMERGENCY GENERATOR 227. |
| 11) PLEASE ADVISE WHAT THE OPEN SHAFT |
| SPACE IS FOR ON PAGE A2.2. |
| 12) PLEASE INDICATE COMPLIANCE WITH |
| ATRIUM REQUIREMENTS IN THE LIFE SAFETY |
| CODE. THE DESIGN OF THE ATRIUM IS TO BE |
| DONE BY A LICENSED ENGINEER AND THE |
| PLANS ARE TO BE SIGNED AND SEALED. |
| PLEASE PROVIDE TESTING REQUIREMENTS AND |
| EQUIPMENT THAT WILL BE NEEDED TO TEST |
| THE ATRIUM SMOKE EXHAUST SYSTEM. PLEASE |
| INDICATE WHAT THE FIREFIGHTERS ATRIUM |
| OVERRIDE PANEL WILL LOOK LIKE. ALSO |
| PLEASE INDICATE THE NUMBER OF REQUIRED |
| AIR CHANGES THAT ARE REQUIRED. |
| 13) PLEASE PROVIDE INTERIOR FINISH |
| CLASSIFICATION INFORMATION. |
| 14) ELEVATORS TO COMPLY WITH ANSI A17.1. |
| PHASE ONE AND PHASE TWO ELEVATOR RECALL |
| WILL BE REQUIRED. |
| 15) ALL STAIRS TO COMPLY WITH NEW STAIRS |
| NFPA 101, THE LIFE SAFETY CODE, 1985 |
| EDITION. |
| 16) PLEASE INDICATE WHAT THE RAISED |
| PLATFORM ON THE NORTH INTERIOR |
| ELEVATION WILL BE USED FOR. |
| 17) NATURAL GAS INSTALLATION TO COMPLY |
| WITH NFPA 54. |
| 18) FIRE SPRINKLER DRAWINGS NOT SIGNED |
| AND SEALED. NO HYDRAULIC CALCULATIONS |
| PROVIDED WITH PLANS. PLEASE PROVIDE |
| MORE DETAILS ON PRE-ACTION SPRINKLER |
| SYSTEM. |
| 19) PLEASE PROVIDE MORE DETAILS FOR THE |
| TEMPORARY RELOCATION OF THE FIRE PUMP |
| AND FIRE MAIN. IF APPROVED BY THIS |
| OFFICE, WHEN DOES THIS ACTIVITY OCCUR. |
| 20) THE CHILLER ROOM IS TO BE EQUIPPED |
| WITH APPROPRIATE SIGNAGE, ALARMS, AND |
| HAVE SELF-CONTAINED BREATHING APPARATUS |
| SINCE REFRIGERATOR LEAK DETECTION IS |
| NOTED ON THE PLANS. |
| |
| CAPTAIN MIKE CARSILLO |
| 659-8096,EXT.8497 |
| 835-2910 |