Plan Review Notes
Plan Review Notes For Permit 01021024
Permit Number 01021024
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-01 00:00:001) PLEASE INDICATE PROPOSED FIRE RESCUE
 INGRESS AND EGRESS POINTS TO THE NEW
 ADDITION.
 2) PLEASE LOCATE EXISTING FIRE HYDRANT
 LOCATIONS FOR MUSEUM.
 3) PLEASE PROVIDE MORE DETAILS ON GATES
 LOCATED NEAR SOUTH DIXIE FOR DROP OFF
 LANE.
 4) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 5) MAXIMUM TRAVEL DISTANCE NOTE ON CD1.1
 IS INCORRECT. MAXIMUM TRAVEL DISTANCE
 IN SPRINKLERED BUILDINGS OF THIS TYPE IS
 200 FEET.
 6) PLEASE FURTHER CLARIFY CD1.1. EXIT
 SIGNS AND DOORS MUST BE SHOWN. PLAN WAS
 DIFFICULT TO FOLLOW.
 7) PLEASE ADVISE HOW DEMOLITION WILL
 OCCUR WHEN THE MUSEUM IS OPEN.
 8) PLEASE PROVIDE PRODUCT APPROVAL FOR
 ONE HOUR FIRE RATED GLAZING IN CORRIDOR
 101.
 9) PLEASE INDICATE HOW ILLUMINATED
 EXIT SIGNS WILL BE INSTALLED IN OFFICES
 230 DUE TO HEADROOM ISSUES.
 10) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR 227.
 11) PLEASE ADVISE WHAT THE OPEN SHAFT
 SPACE IS FOR ON PAGE A2.2.
 12) PLEASE INDICATE COMPLIANCE WITH
 ATRIUM REQUIREMENTS IN THE LIFE SAFETY
 CODE. THE DESIGN OF THE ATRIUM IS TO BE
 DONE BY A LICENSED ENGINEER AND THE
 PLANS ARE TO BE SIGNED AND SEALED.
 PLEASE PROVIDE TESTING REQUIREMENTS AND
 EQUIPMENT THAT WILL BE NEEDED TO TEST
 THE ATRIUM SMOKE EXHAUST SYSTEM. PLEASE
 INDICATE WHAT THE FIREFIGHTERS ATRIUM
 OVERRIDE PANEL WILL LOOK LIKE. ALSO
 PLEASE INDICATE THE NUMBER OF REQUIRED
 AIR CHANGES THAT ARE REQUIRED.
 13) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 14) ELEVATORS TO COMPLY WITH ANSI A17.1.
 PHASE ONE AND PHASE TWO ELEVATOR RECALL
 WILL BE REQUIRED.
 15) ALL STAIRS TO COMPLY WITH NEW STAIRS
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 16) PLEASE INDICATE WHAT THE RAISED
 PLATFORM ON THE NORTH INTERIOR
 ELEVATION WILL BE USED FOR.
 17) NATURAL GAS INSTALLATION TO COMPLY
 WITH NFPA 54.
 18) FIRE SPRINKLER DRAWINGS NOT SIGNED
 AND SEALED. NO HYDRAULIC CALCULATIONS
 PROVIDED WITH PLANS. PLEASE PROVIDE
 MORE DETAILS ON PRE-ACTION SPRINKLER
 SYSTEM.
 19) PLEASE PROVIDE MORE DETAILS FOR THE
 TEMPORARY RELOCATION OF THE FIRE PUMP
 AND FIRE MAIN. IF APPROVED BY THIS
 OFFICE, WHEN DOES THIS ACTIVITY OCCUR.
 20) THE CHILLER ROOM IS TO BE EQUIPPED
 WITH APPROPRIATE SIGNAGE, ALARMS, AND
 HAVE SELF-CONTAINED BREATHING APPARATUS
 SINCE REFRIGERATOR LEAK DETECTION IS
 NOTED ON THE PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved