Plan Review Notes
Plan Review Notes For Permit 01021024
Permit Number 01021024
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-07 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE TO
 BESIGNED AND SEALED PER F.A.C 471.025/
 61G15-23.002. BY AN ENGINEER.
  
 2)NOTE: PLEASE SEE 230-95 FOR GFI
 PROTECTION OF SERVICE.
  
 3)NOTE: PLEASE CLARIFY MEANS OF
 DISCONNECT FOR GENERATOR, GROUPED WITH
 MAIN PER 230-72 AND REQ`MENTS FOR DISC
 PER 230-76 AND 230-79.
  
 4)NOTE: PLEASE SHOW ALL CONDUIT/WIRE
 SIZES ON LINE DIAGRAM.
  
 5)NOTE: PLEASE SUBMIT COMPLETE PANEL
 SCHEDULES AND PLANS FOR SERVICE.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCULATIONS ECT EQUIPMENT LOADS ETC
 ETC ETC,,,,
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372