Plan Review Notes For Permit 01021024 |
Permit Number |
01021024 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-07 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE TO | | BESIGNED AND SEALED PER F.A.C 471.025/ | | 61G15-23.002. BY AN ENGINEER. | | | | 2)NOTE: PLEASE SEE 230-95 FOR GFI | | PROTECTION OF SERVICE. | | | | 3)NOTE: PLEASE CLARIFY MEANS OF | | DISCONNECT FOR GENERATOR, GROUPED WITH | | MAIN PER 230-72 AND REQ`MENTS FOR DISC | | PER 230-76 AND 230-79. | | | | 4)NOTE: PLEASE SHOW ALL CONDUIT/WIRE | | SIZES ON LINE DIAGRAM. | | | | 5)NOTE: PLEASE SUBMIT COMPLETE PANEL | | SCHEDULES AND PLANS FOR SERVICE. | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 7)NOTE: PLEASE SUBMIT COMPLETED LOAD | | CALCULATIONS ECT EQUIPMENT LOADS ETC | | ETC ETC,,,, | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|