Plan Review Notes
Plan Review Notes For Permit 01021024
Permit Number 01021024
Review Stop B
Sequence Number 1
Notes
Date Text
2001-03-19 00:00:00A COMPLETE PLAN PREVIEW FOR CODE
 COMPLIANCE WAS NOT POSSIBLE SINCE THE
 PLANS AND SPECIFICATIONS AND PROVIDED
 ARE INCOMPLETE.
  
 THE CODE PLAN SHEET CD1.1 APPEARS TO USE
 THE NOMINAL WIDTHS OF THE EGRESS DOORS
 AND OPENINGS.SBC 1003.2 REQUIRES THE
 CLEAR WIDTH TO BE USED.
  
 SHEET A1.2.WHERE WILL THE NEW STAIR #
 4 DISCHARGE?
  
 THE OVAL STAIR REQUIRES AN ENCLOSURE
 SINCE IT PENETRATES MORE THAN 2
 STORIES.SEE SBC 705.2.2.H3 IMPLIES
 AN ATRIUM.IF SO PROVIDE ALL
 INFORMATION AND CALCULATIONS AT TIME OF
 PERMIT.SEE SBC 414.1.
  
 SHEET A1.4.THE ROOF AND OVERFLOW
 DRAINS MUSTBE SIZED TO THE 1994
 STANDARD PLUMBING CODE.
  
 SHEET A2.1A.DETAILS FOR THE ATTACHMENT
 OF THE WOOD CEILING WILL BE NECESSARY.
  
 A3.1.SPECIFIC CONNECTION DETAILS WILL
 BE REQUIRED FOR THE CAST STONE AND THE
 "COMPONENT" PANELS.
  
 THIS IS A THRESHOLD BUILDING AND WILL
 REQUIRE A THRESHOLD INSPECTOR AND
 INSPECTION PLAN.SEE FS 553.71.
  
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY.CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 PRODUCT APPROVALS AND TEST REPORTS ARE
 REQUIRED FOR THE WINDOWS, ROOF
 COVERINGS AND THE HURRICANE MISSILE
 IMPACT PROTECTION SYSTEM.