Plan Review Notes For Permit 01020853 |
Permit Number |
01020853 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-06 00:00:00 | 1) PROVIDE PERMIT AND SHOP DRAWINGS | | FOR FIRE ALARM REMODEL. | | 2) FIRE ALARM NOTES INDICATES CLASS B, | | STYLE C FIRE ALARM CIRCUITS. ONLY CLASS | | A, STYLE D CIRCUITS WILL BE PERMITTED. | | 3) DUCT SMOKE DETECTOR IS REQUIRED TO | | BE CONNECTED TO FIRE ALARM SYSTEM. | | 4) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS | | TO COMPLY WITH CITY CODE REQUIREMENTS. | | 5) PLEASE PROVIDE PRODUCT APPROVALS FOR | | TWO HOUR RATED WALL FIRE SHUTTER LOCATED | | AT OFFICE 104. | | 6) PLEASE INDICATE STORAGE ARRANGEMENTS | | FOR WAREHOUSE 110 AREA. | | | | PLAN REVIEW STOP DONE ON ENGINEERING | | COMPUTER BECAUSE FIRE COMPUTER IS DOWN. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|