Plan Review Notes
Plan Review Notes For Permit 01020853
Permit Number 01020853
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-06 00:00:001) PROVIDE PERMIT AND SHOP DRAWINGS
 FOR FIRE ALARM REMODEL.
 2) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C FIRE ALARM CIRCUITS. ONLY CLASS
 A, STYLE D CIRCUITS WILL BE PERMITTED.
 3) DUCT SMOKE DETECTOR IS REQUIRED TO
 BE CONNECTED TO FIRE ALARM SYSTEM.
 4) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR
 TWO HOUR RATED WALL FIRE SHUTTER LOCATED
 AT OFFICE 104.
 6) PLEASE INDICATE STORAGE ARRANGEMENTS
 FOR WAREHOUSE 110 AREA.
  
 PLAN REVIEW STOP DONE ON ENGINEERING
 COMPUTER BECAUSE FIRE COMPUTER IS DOWN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910