Plan Review Notes For Permit 01020853 |
Permit Number |
01020853 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-06 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT CLARIFICATION ON | | PANELS "H1A" AND "L1A" BOTH SHOW IN | | UPPER LEFT HAND CORNERS OF SCHEDULES | | MAIN: 225/MAIN LUGS ONLY. PLEASE | | CLARIFY?? "H1A" DOESN'T NEED MAIN, | | WHILE"L1A" DOES. PLEASE SHOW. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | AIC RATINGS ARE SHOWN FOR BOTH PANELS, | | BUT NOT FOR MAIN DISCONNECT ? PLEASE | | SUBMIT AND SHOW.215-5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|