Plan Review Notes
Plan Review Notes For Permit 01020819
Permit Number 01020819
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-02-21 00:00:001) SMOKE DETECTOR REQUIRED ABOVE FIRE
 ALARM CONTROL PANEL.
 2) SMOKE DETECTORS ARE REQUIRED IN ALL
 LOUNGES, RECREATION AREAS AND SLEEPING
 ROOMS OF THE CENTER.
 3) SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
 4) IF 100 OR MORE DAY CARE STUDENTS ARE
 PRESENT THEN THE REQUIRED FIRE ALARM
 SYSTEM IS TO BE MONITORED.
 5) SYSTEM TO BE TESTED IN THE PRESENCE
 OF A FIRE RESCUE REPRENSATIVE AFTER
 INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910