2001-02-24 00:00:00 | PROVISO; | | | | 1.R/A REQUIRED IN MASTER BEDROOM. | | | | 2.MISSING DROP IN BEDROOM #2. | | | | 3.1455 CFM'S WITH MISSING DROP. A/H | | ONLY CAPABLE OF 1400 CFM'S. | | | | REVISED DRAWINGS BEFORE FINAL A/C | | INSPECTION. | | | | A/C PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8377 |
|