Plan Review Notes
Plan Review Notes For Permit 01020772
Permit Number 01020772
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-05 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 MISSING THE REQ`D MEANS OF EGRESS
 LIGHTING
 PER 210-70. ENTERING HOUSE/FOYER HALLWAY
 DOWN TO BEDROOM ETC.
  
 2)NOTE: PLEASE NOTE THAT THE AIC RATING
 SUBMITTED IS SHOWN FOR BRKRS ONLY?
 PLEASE SUBMIT ALL EQUIPMENT AIC RATINGS
 INCLUDING MAIN DISCONNECT. PER 110-9
 AND215-5
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372