Plan Review Notes For Permit 01020772 |
Permit Number |
01020772 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-03-05 00:00:00 | ***************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE | | MISSING THE REQ`D MEANS OF EGRESS | | LIGHTING | | PER 210-70. ENTERING HOUSE/FOYER HALLWAY | | DOWN TO BEDROOM ETC. | | | | 2)NOTE: PLEASE NOTE THAT THE AIC RATING | | SUBMITTED IS SHOWN FOR BRKRS ONLY? | | PLEASE SUBMIT ALL EQUIPMENT AIC RATINGS | | INCLUDING MAIN DISCONNECT. PER 110-9 | | AND215-5 | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | MECHANICAL CODE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|