2001-02-15 00:00:00 | 1) THE SMOKE DETECTORS WHEN INSTALLED | | ARE TO BE A MINIMUM OF THREE FEET FROM | | AIR CONDITIONER DIFFUSERS. | | 2) TAMPER SWITCHES ARE TO BE PROVIDED | | ON THE BACKFLOW DEVICE. | | 3) THE FIRE ALARM SYSTEM AND FIRE | | SPRINKLER SYSTEM ARE TO BE MONITORED | | BY A LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 4) FIRE ALARM SYSTEM TO BE CLASS A OR | | ADDRESSABLE. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|