2001-03-01 00:00:00 
 PROVISO:
  
 HEAT PUMPS REQUIRE A DRAIN PAN WITH
 OVERFLOW PROTECTION SUCH AS FLOAT
 SWITCH OR SECONDARY DRAIN LINE, AS
 PER 1997 SMC 304.8.6.1.
  
 REFERENCE DRAWING M0.1, NOTE 12 -
 AS PER NFPA 90A 4-4.4.3(A), FAN SHUT
 DOWN SHALL HAVE NOTIFICATION TO HORN
 AND STROBE IN NORMALLY OCCUPIED
 AREAS.