Notes |
Date |
Text |
2001-03-01 00:00:00 | | | PROVISO: | | | | HEAT PUMPS REQUIRE A DRAIN PAN WITH | | OVERFLOW PROTECTION SUCH AS FLOAT | | SWITCH OR SECONDARY DRAIN LINE, AS | | PER 1997 SMC 304.8.6.1. | | | | REFERENCE DRAWING M0.1, NOTE 12 - | | AS PER NFPA 90A 4-4.4.3(A), FAN SHUT | | DOWN SHALL HAVE NOTIFICATION TO HORN | | AND STROBE IN NORMALLY OCCUPIED | | AREAS. |
|