2001-02-13 00:00:001) PLEASE INDICATE THE INSTRUCTIONS
 THAT WILL BE GIVEN FOR THE TAPED
 MESSAGE PORTION OF THE FIRE ALARM
 SYSTEM.
 2) THE FIRE ALARM SYSTEM AND FIRE
 SPRINKLER SYSTEM TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 3) HOW IS THE INSTALLATION OF THE NEW
 FIRE ALARM SYSTEM GOING TO BE PERFORMED
 AND HOW LONG WILL THE EXISTING FIRE
 ALARM SYSTEM BE INSERVICE. WILL ANY
 GAPS IN COVERAGE OCCUR.
 4) SMOKE DETECTORS MUST BE INSTALLED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITONING DIFFUSERS.
 5) THE NEW ATRIUM FIRE ALARM EQUIPMENT
 MUST BE IDENTIFIED AS HOW IT EFFECTS THE
 OPERATION OF THE REQUIRED SMOKE CONTROL/
 EXHAUST FEATURES OF THE ATRIUM PORTION
 OF THE BUILDING.
 6) PLEASE INDICATE SEQUENCE OPERATIONS
 FOR THE STAIRWAY FANS.
 7) LOCKS ON EXIT DOORS THAT ARE
 INTERFACED WITH THE FIRE ALARM SYSTEM
 ARE TO MEET SPECIAL LOCKING ARRANGEMENTS
 PER THE LIFE SAFETY CODE.
 8) THE DUCT SMOKE DETECTORS WHEN
 ACTIVATED ARE TO SHUT DOWN ALL AIR
 HANDLING EQUIPMENT AND ACTIVATE THE
 FIRE ALARM SYSTEM.
 9) WILL THE FIRE ALARM SYSTEM WHEN
 ACTIVATED, ALERT THE FLOOR OF INCIDENT,
 THE FLOOR ABOVE AND BELOW OR THE WHOLE
 BUILDING.
 10) ARE ALL HOOD EXTINGUISHING SYSTEMS
 AT THE COMPLEX TIED INTO THE FIRE
 ALARM SYSTEM.
  