2001-03-09 00:00:00TRUSSES UNSAT
  
 1) GE1 AND T1 ARE FOR PITCHED ROOF AND
 FLAT ROOF IS SHOWN ON PRINTS.
  
 2) TRUSS LAYOUT AND DRAWINGS INDICATE A
 VAULTED CEILING IN THE GARAGE. THIS IS
 NOT INDICATED ON PLANS.
  
 3) NO ANCHORS ARE INDICATED FOR THE (2)
 INTERIOR BEARING POINTS FOR T-14 OR THE
 (1) INTERIOR BEARING POINT FOR T-15.
  
 4) THE UPLIFT AT POINT 1 FOR T-16 IS
 1519# ON TRUSS DRAWINGS THE SCHEDULE
 VALUE OF 1450# IS EXCEEDED.
  
 5) THE UPLIFT AT T-29 EXCEEDS ANCHOR
 SCHEDULE VALUE.
  
 6) TURRENT FRAMING PLAN ON S1 INDICATES
 TA-6 THIS IS NOT LISTED ON SCHEDULE.
  
 7) TRUSS DRAWINGS GIVES UPLIFT OF 1457#
 FOR EACH END OF TG-1, TA-9 ANCHOR
 INDICATED ON PLANS ONLY PROVIDE FOR
 545#.
  
 PLEASE REVIEW AND CORRECT ANY ERRORS.
  