Plan Review Notes For Permit 01020403 |
Permit Number |
01020403 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-02-28 00:00:00 | ******************* UNSAT ************ | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210-8-A-6. | | | | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | DOES NOT CORRELATE WITH PLANS. MAINS/PAN | | ELS/DISCONNECTS ETC.? PLEASE SUBMIT CLAR | | IFICATION. | | | | 5)NOTE: PLEASE NOTE THAT NO MAIN DISCONN | | ECT IS SHOWN ON RISER DIAGRAM WHICH IS R | | EQ`D BY 225-31. | | | | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL PER 250-50. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|