Plan Review Notes
Plan Review Notes For Permit 01020403
Permit Number 01020403
Review Stop E
Sequence Number 1
Notes
Date Text
2001-02-28 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 DOES NOT CORRELATE WITH PLANS. MAINS/PAN
 ELS/DISCONNECTS ETC.? PLEASE SUBMIT CLAR
 IFICATION.
  
 5)NOTE: PLEASE NOTE THAT NO MAIN DISCONN
 ECT IS SHOWN ON RISER DIAGRAM WHICH IS R
 EQ`D BY 225-31.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL PER 250-50.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372