Plan Review Notes For Permit 01020278 |
Permit Number |
01020278 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-04-18 00:00:00 | ******************PROVISO*************** | | | | DRAWING M2.2, A/C ROOF EQUIPMENT | | MOUNTING DETAIL - SHALL COMPLY WITH | | AMENDED 1997 SMC 304.2.5, MOUNTING | | HEIGHT SHALL BE A MINIMUM OF 18" FROM | | ROOF SURFACE TO BOTTOM OF SUPPORT BEAM. |
|