Plan Review Notes For Permit 01020278 |
Permit Number |
01020278 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-02-28 00:00:00 | PLUMBING PLAN REVIEWDENIED | | COMMENTSREFERENCE STD PLBG CODE 94 | | (1) SHT PO.1 DETAIL P3.1 | | COMPLY W/ SEC 501.7 WTR HTR READLY | | ACCESSIBLE,PROVIDE A DETAIL OF A WORKING | | PLATFORM WITH A SHIPS LADDER FIXED IN | | PLACE. | | DIELECTRIC UNIONS NOT PERMITTED, USE A | | DIELECTRIC NIPPLE OR COUPLING. | | PAN DRAIN MIN SIZE 1". | | (2) SHT P5.1 AIR CHAMBERS,COMPLY WITH | | SEC 607.8.3 AIR CHAMBERS READLY ACCESS- | | IBLE, SHOW A TYPICAL DETAIL HOW TO | | RESTORE AIR IN THE AIR CHAMBER WHEN IT | | BECOMES WATER LOGGED. | | (3)SHT P5.1 ISOMETRIC DRWG. SEC 901.2 | | MOP SINK NOT VENTED. | | END OF COMMENTS QUESTIONS CONTACT | | PAUL SCHMITZ 561-659-8096X 8233 |
|