Plan Review Notes
Plan Review Notes For Permit 01020278
Permit Number 01020278
Review Stop P
Sequence Number 1
Notes
Date Text
2001-02-28 00:00:00PLUMBING PLAN REVIEWDENIED
 COMMENTSREFERENCE STD PLBG CODE 94
 (1) SHT PO.1 DETAIL P3.1
 COMPLY W/ SEC 501.7 WTR HTR READLY
 ACCESSIBLE,PROVIDE A DETAIL OF A WORKING
 PLATFORM WITH A SHIPS LADDER FIXED IN
 PLACE.
 DIELECTRIC UNIONS NOT PERMITTED, USE A
 DIELECTRIC NIPPLE OR COUPLING.
 PAN DRAIN MIN SIZE 1".
 (2) SHT P5.1 AIR CHAMBERS,COMPLY WITH
 SEC 607.8.3 AIR CHAMBERS READLY ACCESS-
 IBLE, SHOW A TYPICAL DETAIL HOW TO
 RESTORE AIR IN THE AIR CHAMBER WHEN IT
 BECOMES WATER LOGGED.
 (3)SHT P5.1 ISOMETRIC DRWG. SEC 901.2
 MOP SINK NOT VENTED.
 END OF COMMENTS QUESTIONS CONTACT
 PAUL SCHMITZ 561-659-8096X 8233