Plan Review Notes
Plan Review Notes For Permit 01020278
Permit Number 01020278
Review Stop M
Sequence Number 1
Notes
Date Text
2001-02-21 00:00:00*****************DENIED*****************
  
 PROVIDE OUTSIDE AIR CALCULATION AS PER
 ASHRAE 62-89.
  
 PROVIDE AIR BALANCE SCHEDULE AS PER 1997
 SMC 501.2.
  
 DRAWING #M2.1 AHU-3 AND AHU-8 DO NOT
 INDICATE CFM FOR EVERY DROP.