Plan Review Notes For Permit 01020262 |
Permit Number |
01020262 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-02-21 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT REQUIRED. | | | | NOTE:AS PER 1997 SMC 609.1.1 THERE | | SHALL BE NO COMBUSTIBLES ABOVE CEILING | | IN RETURN AIR PLENUM. | | | | AS PER 1997 SMC 304.8.6.1 OVER FLOW | | PROTECTION IS REQUIRED FOR DX-2. | | | | PROVIDE INFORMATION FOR BACKFLOW | | PREVENTION DRAWING M-4, NOTE 16 THRU 18. | | | | PROVIDE AIR BALANCE SCHEDULE AS WELL AS | | OUTSIDE AIR CALCULATIONS TO SHOW | | COMPLIANCE WITH ASHRAE 62-89. | | | | AS PER 1997 SMC 609.1.1 - DUCT SMOKE | | DETECTORS REQUIRED FOR FAN SHUT DOWN | | WITH NOTIFICATION TO ALARM/STROBE AS | | PER NFPA 90A 4-4.4.3. |
|