Plan Review Notes
Plan Review Notes For Permit 01020102
Permit Number 01020102
Review Stop P
Sequence Number 2
Notes
Date Text
2001-06-09 00:00:00PLUMBING PLAN REVIEW"DENIED 2ND X"
 (1) COMMENTS DATED 02-27-01 HAVE NOT
 BEEN ADDRESSED.
 (2) SHTA5,A6,PROVIDE CALCULATIONS FOR
 SIZING INDIVIDUAL ROOF DRAINS,SPC 94 TAB
 1108.1.2, USING FIG 1108.4 RATE OF RAIN
 FALL, FOR WPB AREA.
 SECONDARY ROOF DRAINS (SCUPPERS),SHOW
 CALCULATIONS FOR INDIVIDUAL DRAINS.
 SPC 94 SEC 1109.1 & FIG 1109.3 RATE OF
 RAIN FALL,FOR WPB AREA.
 (3) SHTA 11, METER & PUMP RM ROOFS,
 PRIMARY & SECONDARY DRAINS NOT SHOWN.
 (4) SHT P2.1, KEY NOTES,REFERENCES CIVIL
 DRWGS FOR CONTINUATION OF STORM DRAINS,
 PLEASE INDICATE WHICH SHTTHIS IS ON.
 (5) SHT P2.1 & P2.2, SPC 94 SEC 407.1.1
 MINIMUM FACILITIES,NUMBER OF EA TYPE OF
 FIXTURE SHALL BE INSTALLED,USE TAB 407.
 (6) SHT P0.1 PLBG NOTES 13,18,REFERENCE
 AIR CHAMBERS,SHOW A DETAIL OF APPROVED
 AIR CHAMBER AND HOW IT WILL BE RECHARGE-
 ABLE,ACCESSIBLE SPC 94 SEC 607.8.3
 (7) SHTS PP1 TO 4,PROVIDE INFORMATION ON
 IRRIGATION SYSTEM, SPC 94 SEC 104.3
 LOCATION AND TYPE OF BACK FLOW PREVENTER
 END OF COMMENTS PAUL SCHMITZ